Plan Review Notes
Plan Review Notes For Permit 21081684
Permit Number 21081684
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-07 12:10:0709/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BUILDING WAS CONSTRUCTED UNDER THE FAIR HOUSING
 ACT. WOULD YOU PLEASE INDICATE ON PLANS WHICH DESIGN
 SPECIFICATION ( "A" OR "B" OF THE ACT) WAS USED IN THE
 ORIGINAL DESIGN OF THESE UNITS? TELL US WHICH USABLE
 BATHROOM IN THE DWELLING UNITS AND THE PROPOSED
 ALTERATION IN THE BATHROOM SHALL ALSO COMPLY WITH THE
 FAIR HOUSING ACT. THIS NEEDS TO BE DETERMINED BY
 RESEARCHING WHEN THE BUILDING WAS BUILT AND REQUESTING
 PLANS FROM THIS CITY?S WEBSITE. THIS MAY INCUR A FEE
 AND TIME TO RETRIEVE ALL THIS INFORMATION. IT IS UP TO
 THE ARCHITECT TO REQUEST THE INFORMATION AND DETERMINE
 IF THE LEVEL OF ACCESSIBILITY IS ALTERED. WE REQUIRE TO
 SHOW THE DIMENSION OF THE CLEAR FLOOR SPACE IN THE
 BATHROOM IN FRONT OF EACH FIXTURE IN THAT BATHROOM. THE
 RESEARCH WILL TELL IF IT'S AN A OR B TYPE BATHROOM.
  
 2. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 PROVIDES AN OPTION FOR CHANGING AN FHA COMPLIANCE
 STRUCTURE. THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE
 THAT THE PROPOSED BATHROOM DESIGN DOES NOT MEET THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES REQUIREMENTS. THE
 OWNER AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT
 THE TIME OF SALE IF SO, REQUESTED BY THE BUYER. THIS
 WILL BE IN A LETTER-TYPE FORMAT SIGNED AND NOTARIZED BY
 THE OWNER. WE PROVIDE A SAMPLE LETTER, AND IT MUST BE
 SUBMITTED TO THE BUILDING DEPARTMENT OF THE CITY OF
 WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL TO
 [email protected], AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT.
  
 3. ON SHEET P-1;
 A. UNDER GENERAL PLUMBING NOTES, IT REFERS TO THE 2017
 PLUMBING CODE. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER
 DIAGRAM FOR SANITARY AND PLUMBING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING?
  
 C. THE WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, 2020 FBC SEC. R
 2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE
 SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS
 PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  