Plan Review Notes
Plan Review Notes For Permit 21081590
Permit Number 21081590
Review Stop M
Sequence Number 1
Notes
Date Text
2021-09-01 08:34:071ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21081590
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPLICATION STATES THIS IS FOR 4 WALK-INS. THE
 SITE LOCATION DRAWING HAS 3 WALK-INS COLORED IN YELLOW
 INDICATING THEY ARE THE COOLERS. THEY ARE THE FREEZER,
 COOLER AND LIQUID STORAGE. THE BANQUET COOLER AND THE
 BEER COOLER IS NOT IDENTIFIED AS BEING INCLUDED IN THIS
 APPLICATION ALTHOUGH 005 ELEVATION SECTIONS DETAIL
 SHEET IS A DRAWING OF THE BEER COOLER. IS THERE ONLY 3
 WALK-INS BEING REPLACED FOR THIS PROJECT?
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  