2021-09-30 11:47:00 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 21081487 |
| 9/30/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE PLAN INDICATES AN EXISTING GAS LINE TO THE |
| SUMMER KITCHEN, HOWEVER THE WPB BUILDING DEPT. RECORDS |
| DO NOT SHOW A PREVIOUS GAS PERMIT OR PLANS AT THE |
| RESIDENCE. PLEASE PROVIDE A COMPLETE GAS RISER DRAWING |
| THAT INCLUDES ALL NEW AND EXISTING GAS PIPING AND |
| APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & G2412.4 |
| FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- THE |
| RISER SHALL SHOW: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 6) INDICATE THE MAKES AND MODELS OF REGULATORS TO BE |
| INSTALLED ON THE SYSTEM AND SUBMIT MANUFACTURER?S |
| SPECIFICATIONS MARKED UP TO SHOW THE SELECTED MODELS, |
| AND INPUT AND OUT PIPE SIZES AND PRESSURES- SECTION |
| G2421.2 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |