Plan Review Notes For Permit 21081550 |
Permit Number |
21081550 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-10-16 11:05:54 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC R 301, INSTALLATION PROPOSED NOT CLEAR, REVISE | | THE INSTALLATION SCHEDULE TO CLARIFY: | | | | THE ADDRESS ON THE SCHEDULE DOES NOT MATCH THE ADDRESS | | ON THE APPLICATION | | HORIZONTAL SPAN IS PROPOSED, ARE YOU INSTALLING THE | | ACCORDIONS SO THEY OPEN UP AND DOWN? SPAN IS EQUAL TO | | BLADE LENGTH | | CONFIRM THAT THE DIMENSIONS PROVIDED ARE WIDTH X | | HEIGHT, DUE TO PROPOSED INSTALLATION THIS IS NOT CLEAR | | HOW HAVE YOU DETERMINED THAT THE SUBSTRATE IS CONCRETE? | | IF MOUNTED ON THE SIDES, THIS IS TYPICALLY FILLED | | CELLS. | | | | | | 2. SEE PAGE 13, A FACTOR OF .9 REQUIRED FOR 3" EDGE | | DISTANCE. 10" IS PROPOSED BUT STATES THAT IT HAS A | | FACTOR OF .9. THE FACTOR IS REQUIRED BUT NOT APPLIED. | | 10" X .9 = 9". THE SCHEDULE SHOULD PROPOSE 9". | | | | | | |
|