2021-09-24 10:21:211ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THE
 EXPOSURE CATEGORY IS C AND THE VULT. WIND SPEED IS 170
 MPH. FBC-R301.1
 2) THE NEGATIVE UPLIFT PRESSURES IN THE ROOF PRESSURE
 CHART ON SHEET S.1 APPEAR TO BE LOW. FBC-R301.2.1
 3) THE RAFTER SPANS OF JUST UNDER 18 FEET FOR THE 2X10S
 AT 16" OC APPEARS TO BE EXCESSIVE BASED ON THE DEAD
 LOADS OF THE ROOF COVERING AND THE 7/8" STUCCO CEILING
 ALONG WITH THE LIVE LOADS. SUBMIT SIGNED AND SEALED
 CALCULATIONS FROM THE ENGINEER. FBC AMENDMENTS
 107.2.1.2
 4) THE DOUBLE 2X10 LOAD BEARING HEADERS THAT ARE
 SUPPORTING THE ROOF FRAMING ARE SPANNING MORE THAN 12
 FEET. SUBMIT SIGNED AND SEALED CALCULATIONS TO SHOW
 THEY ARE CAPABLE OF SUPPORTING THE LOADS. FBC
 AMENDMENTS 107.2.1.2
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  