2021-09-24 10:21:21 | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THE | | EXPOSURE CATEGORY IS C AND THE VULT. WIND SPEED IS 170 | | MPH. FBC-R301.1 | | 2) THE NEGATIVE UPLIFT PRESSURES IN THE ROOF PRESSURE | | CHART ON SHEET S.1 APPEAR TO BE LOW. FBC-R301.2.1 | | 3) THE RAFTER SPANS OF JUST UNDER 18 FEET FOR THE 2X10S | | AT 16" OC APPEARS TO BE EXCESSIVE BASED ON THE DEAD | | LOADS OF THE ROOF COVERING AND THE 7/8" STUCCO CEILING | | ALONG WITH THE LIVE LOADS. SUBMIT SIGNED AND SEALED | | CALCULATIONS FROM THE ENGINEER. FBC AMENDMENTS | | 107.2.1.2 | | 4) THE DOUBLE 2X10 LOAD BEARING HEADERS THAT ARE | | SUPPORTING THE ROOF FRAMING ARE SPANNING MORE THAN 12 | | FEET. SUBMIT SIGNED AND SEALED CALCULATIONS TO SHOW | | THEY ARE CAPABLE OF SUPPORTING THE LOADS. FBC | | AMENDMENTS 107.2.1.2 | | 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. | | |
|