Plan Review Notes
Plan Review Notes For Permit 21081463
Permit Number 21081463
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-12 12:50:5310/12/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS A RECORD FOR SUITE
 100 AS A DIFFERENT LOCATION, SO PLEASE ADDRESS THE AD
 STOP COMMENTS.
  
 2. WOULD YOU PLEASE PROVIDE WHAT TYPE OF OCCUPANCY THIS
 INTERIOR BUILD-OUT WILL BE AND THE OCCUPANCY LOAD WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. WOULD YOU PLEASE GIVE THE LEVEL OF ALTERATION PER
 2020 FLORIDA EXISTING BUILDING CODE 301.1.
  
 4. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF
 FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE
 OF THE BUILDING OR SPACE PER TABLE 403.1 MINIMUM NUMBER
 OF FIXTURES.
  
 5. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING
 THROUGH RATED WALLS OR THE FLOORS. PLEASE SUBMIT THE
 COMPLETE ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
  
 6. ON SHEET P-1;
  
 A. UNDER GENERAL PLUMBING, NOTE NUMBER TWO REFERS TO
 THE 2017 BUILDING CODE. WOULD YOU PLEASE CORRECT TO THE
 CURRENT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THERE IS VERBIAGE ABOUT TUB AND SHOWER VALVES THAT
 DO NOT DO WITH THIS PROJECT.
  
 C. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC WATER
 RISER DIAGRAM PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 D. THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER
 PIPING, FROM THE SOURCE OF HOT WATER TO THE FIXTURES,
 EXCEEDS 50 FEET. RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
  
 E. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES
 SHALL BE SUPPLIED TO THE SOURCE. THERE IS A TABLE THAT
 LIMITS THE SOURCE AND THE OUTLET; PLEASE REFER TO TABLE
 405.5.1 FOR THE MAXIMUM ALLOWABLE PIPE LENGTH METHOD
 AND SIZE ACCORDANTLY.
  
 F. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 SHALL BE IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT
 IN THE FLORIDA ENERGY CODE SEC. C404.6.1.
  
 G. RECIRCULATING SYSTEM, THE PIPING SHALL BE INSULATED
 IN ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING
 OF A CIRCULATING PER C404.4 (A) INSULATION OF PIPING.
  
 I. WOULD YOU PLEASE SHOW LOCATIONS OF WATER HAMMER
 ARRESTORS PER THE 2020 FBC SEC. P604.9
  
 7. ON SHEET P-2;
  
 A. IT SHOWS A NEW SINK, AND IF ONE OF THEM IS A BREAK
 ROOM, PLEASE PROVIDE THE CLEAR FLOOR SPACE AND
 DIMENSION FOR CLEAR FLOOR SPACE OF 30? X 48? PER THE
 2020 FBC SEC. ACC 305.3.
  
 B. PROVIDE CABINET DETAIL SHOWING THE SINK AND OR LAVS
 HEIGHT OF 34 INCHES MAXIMUM PER THE 2020 FBC ACC SEC.
 606.3.
  
 C. IN THE OFFICES, ONE SINK NEEDS TO BE ACCESSIBLE.
 WOULD YOU PLEASE LABEL AND REFER TO LETTER C COMMENTS
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. IF PER THE FIXTURE TABLE A DRINKING FOUNTAIN IS
 REQUIRED OR ONE IS ON THAT FLOOR, SHOW HOW FAR AND THE
 ACCESSIBILITY DIMENSION OF IT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 E. IS THERE AN ICE MAKER OR A COFFEE MAKER, AND IF SO,
 IT SHALL BE EQUIPPED WITH AN IN-LINE VACUUM BREAKER
 THAT COMPLIES WITH ASSE 1024 PER THE 2020 FBC SEC.
 608.13.10.
  
 8. WOULD YOU PLEASE SUBMIT A SLAB REPAIR DETAIL? SHOW
 THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING
 OF THE DOWELS IN THE CENTER. THE REPAIR SHALL ALSO
 INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED
 VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved