2021-10-13 12:31:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 WHAT TYPE OF OCCUPANCY IS THIS? WHAT KIND OF TENNANT?
  
 1) PLEASE SUBMIT AN INTERIOR LIGHTING POWER ALLOWANCE
 CALCULATION.
  
 C405.3.2 INTERIOR LIGHTING POWER ALLOWANCE. THE TOTAL
 INTERIOR LIGHTING POWER ALLOWANCE (WATTS) IS DETERMINED
 ACCORDING TO TABLE C405.3.2(1) USING THE BUILDING AREA
 METHOD, OR TABLE C405.3.2(2) USING THE SPACE-BY-SPACE
 METHOD, FOR ALL AREAS OF THE BUILDING COVERED IN THIS
 PERMIT.
  
 2) OUTLETS WITHIN 6' OF A SINK SHALL BE GFCI PROTECTED
 210.8(B)