Plan Review Notes For Permit 21081463 |
Permit Number |
21081463 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-10-13 12:31:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | WHAT TYPE OF OCCUPANCY IS THIS? WHAT KIND OF TENNANT? | | | | 1) PLEASE SUBMIT AN INTERIOR LIGHTING POWER ALLOWANCE | | CALCULATION. | | | | C405.3.2 INTERIOR LIGHTING POWER ALLOWANCE. THE TOTAL | | INTERIOR LIGHTING POWER ALLOWANCE (WATTS) IS DETERMINED | | ACCORDING TO TABLE C405.3.2(1) USING THE BUILDING AREA | | METHOD, OR TABLE C405.3.2(2) USING THE SPACE-BY-SPACE | | METHOD, FOR ALL AREAS OF THE BUILDING COVERED IN THIS | | PERMIT. | | | | 2) OUTLETS WITHIN 6' OF A SINK SHALL BE GFCI PROTECTED | | 210.8(B) |
|