Plan Review Notes For Permit 21081414 |
Permit Number |
21081414 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-09-21 17:12:26 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FROM PREVIOUS LIST, NO NEW DOCUMENTS UPLOADED. THE S&S | | ENGINEERING WAS UPLOADED TO THE SIGNATURE FOLDER, BUT | | THIS WAS ALREADY REVIEWED IN THE SUPPORTING DOCS FOLDER | | WITH NO ISSUES. THE ISSUE IS THAT THE FLOOR PLAN HAS | | TWO OPENINGS LABELED AS #3, AND THE PRODUCT APPROVAL | | OPTION FOR -60/+80 MARKED ON PAGE 2 OF THE SINGLE HUNG | | PRODUCT APPROVAL. | | | | WHEN RESUBMITTING, REVISE THE FLOOR PLAN SO THERE IS | | ONLY ONE OPENING LABELED #3. | | | | REVISE THE SINGLE HUNG PRODUCT APPROVAL ON PAGE 2 SO | | THAT YOU INDICATE THAT +80/-80 OPTION IS PROPOSED. | | | | COMMENTS FROM PREVIOUS LIST: | | | | 1. FBC B 1609, SEE THE SINGLE HUNG WINDOW PRODUCT | | APPROVAL, PAGE 2. MAX DESIGN PRESSURE +60/-80 IS | | MARKED. THAT DOES NOT MEET THE MINIMUM SPECIFIED BY THE | | ENGINEER (+-62.7), ALSO IS NOT CONSISTENT WITH THE | | WINDOW SCHEDULE. | | | | 2. THE FLOOR PLAN HAS TWO OPENINGS MARKED AS #3, FBC | | 107 PLEASE REVISE. |
|