Plan Review Notes
Plan Review Notes For Permit 21081414
Permit Number 21081414
Review Stop B
Sequence Number 2
Notes
Date Text
2021-09-21 17:12:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST, NO NEW DOCUMENTS UPLOADED. THE S&S
 ENGINEERING WAS UPLOADED TO THE SIGNATURE FOLDER, BUT
 THIS WAS ALREADY REVIEWED IN THE SUPPORTING DOCS FOLDER
 WITH NO ISSUES. THE ISSUE IS THAT THE FLOOR PLAN HAS
 TWO OPENINGS LABELED AS #3, AND THE PRODUCT APPROVAL
 OPTION FOR -60/+80 MARKED ON PAGE 2 OF THE SINGLE HUNG
 PRODUCT APPROVAL.
  
 WHEN RESUBMITTING, REVISE THE FLOOR PLAN SO THERE IS
 ONLY ONE OPENING LABELED #3.
  
 REVISE THE SINGLE HUNG PRODUCT APPROVAL ON PAGE 2 SO
 THAT YOU INDICATE THAT +80/-80 OPTION IS PROPOSED.
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. FBC B 1609, SEE THE SINGLE HUNG WINDOW PRODUCT
 APPROVAL, PAGE 2. MAX DESIGN PRESSURE +60/-80 IS
 MARKED. THAT DOES NOT MEET THE MINIMUM SPECIFIED BY THE
 ENGINEER (+-62.7), ALSO IS NOT CONSISTENT WITH THE
 WINDOW SCHEDULE.
  
 2. THE FLOOR PLAN HAS TWO OPENINGS MARKED AS #3, FBC
 107 PLEASE REVISE.