2021-09-10 17:30:16 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC B 1609, SEE THE SINGLE HUNG WINDOW PRODUCT | | APPROVAL, PAGE 2. MAX DESIGN PRESSURE +60/-80 IS | | MARKED. THAT DOES NOT MEET THE MINIMUM SPECIFIED BY THE | | ENGINEER (+-62.7), ALSO IS NOT CONSISTENT WITH THE | | WINDOW SCHEDULE. | | | | 2. THE FLOOR PLAN HAS TWO OPENINGS MARKED AS #3, FBC | | 107 PLEASE REVISE. |
|