2021-09-10 17:30:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, SEE THE SINGLE HUNG WINDOW PRODUCT
 APPROVAL, PAGE 2. MAX DESIGN PRESSURE +60/-80 IS
 MARKED. THAT DOES NOT MEET THE MINIMUM SPECIFIED BY THE
 ENGINEER (+-62.7), ALSO IS NOT CONSISTENT WITH THE
 WINDOW SCHEDULE.
  
 2. THE FLOOR PLAN HAS TWO OPENINGS MARKED AS #3, FBC
 107 PLEASE REVISE.