2021-09-10 17:20:56RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21081335
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- NEW MODIFIED BITUMEN FLORIDA PRODUCT APPROVAL
 FL16709-R8 SUBMITTED:
 A) BUILDING EXPOSURE: ACCORDING TO SEC. R301.2.1.4
 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE
 "D" NOT "C". REVISE AS REQUIRED.
  
 B) PAGE 25 OF 25 OF MODIFIED BITUMEN FLORIDA PRODUCT
 APPROVAL FL16709-R8 SUBMITTED INDICATES "N/A " FOR ROOF
 ZONE 3 FOR AN ULTIMATE WIND SPEED OF 170MPH IN BUILDING
 EXPOSURE D.
 "N/A" INDICATES THE SYSTEM CANNOT BE USED WITHIN THE
 PRESSURE ZONE. SEE MEANING OF "N/A" ON PAGE 22 OF 25
 UNDER TABLE 7 HEADING.
 NEED TO USE ANOTHER PRODUCT APPROVAL OR PROVIDE SINGED
 AND SEALED RAS 117 CALCULATIONS FOR PRODUCT APPROVAL FL
 2533-R5 AS REQUESTED ON THE FIRST REVIEW.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 **************************************
 ORIGINAL REVIEW COMMENTS:
  
 PLAN REVIEW ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/RPX306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ENHANCED FASTENER CALCULATIONS PER
 LIMITATIONS NOTE 5.7.2 OF FL 2533-R5, PREPARED BY A
 QUALIFIED DESIGN PROFESSIONAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved