Plan Review Notes For Permit 21081320 |
Permit Number |
21081320 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2021-12-20 07:04:41 | 4TH REVIEW FBC-2020 MECHANICAL | | PERMIT-21081320 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) WHERE ARE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS? I ASSUMED THEY WOULD BE INCLUDED IN THE | | CORRECTED ENERGY CALCULATIONS. I DO NOT SEE THEM IN THE | | MAIN HOUSE OR CABANA ENERGY CALCULATIONS. PLEASE | | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. | | FBC EC R403.7.1 | | | | 2) PLEASE SEE COMMENT 3 OF PREVIOUS COMMENTS BELOW: | | | | 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY | | SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION | | OUTSIDE OF THE STRUCTURE. FBC RES M1411.3 | | | | 3) PLEASE PROVIDE THE CFM?S OF THE KITCHEN HOOD. THE | | HOOD MUST MEET THE MAKE UP AIR OF FBC RES M1503.4 IF | | REQUIRED. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|