Plan Review Notes
Plan Review Notes For Permit 21081320
Permit Number 21081320
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-07 10:57:4209/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER
 DIAGRAM FOR WATER AND SANITARY PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 2. WOULD YOU PLEASE SHOW A CONTINUOUS LOOP FOR THE
 RECIRCULATING SYSTEM PER THE 2020 FBC SEC. ER 403.5.1.1
 CIRCULATION SYSTEMS.
  
 3. ON SHEET P 101 A;
  
 A. IT SHOWS A FLOOR DRAIN IN THE HOUSE AND THE GUEST
 HOUSE. THERE IS NO SOURCE OF WATER SHOWN TO THE TRAP
 PRIMER ON THE WATER DIAGRAM. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ON THAT SAME PAGE, IT SHOWS A GD-1 IN GRARAGE AND
 P001 FOR THE PLUMBING SCHEDULE. THERE IS NO SUCH NOTE
 FOR IT. IF IT STANDS FOR GRAVITY DRAIN, WOULD YOU
 PLEASE PROVIDE DETAIL OR MANUFACTURES SPECIFICATION AND
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THIS IS A MULTI-FAMILY DWELLING, AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM. A NOTE ON PLANS FOR A
 SEPARATE PERMIT FOR BACKFLOW WILL BE FINE.
  
 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved