Date |
Text |
2021-09-07 10:57:42 | 09/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER |
| DIAGRAM FOR WATER AND SANITARY PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. |
| |
| 2. WOULD YOU PLEASE SHOW A CONTINUOUS LOOP FOR THE |
| RECIRCULATING SYSTEM PER THE 2020 FBC SEC. ER 403.5.1.1 |
| CIRCULATION SYSTEMS. |
| |
| 3. ON SHEET P 101 A; |
| |
| A. IT SHOWS A FLOOR DRAIN IN THE HOUSE AND THE GUEST |
| HOUSE. THERE IS NO SOURCE OF WATER SHOWN TO THE TRAP |
| PRIMER ON THE WATER DIAGRAM. WOULD YOU PLEASE CORRECT |
| PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| B. ON THAT SAME PAGE, IT SHOWS A GD-1 IN GRARAGE AND |
| P001 FOR THE PLUMBING SCHEDULE. THERE IS NO SUCH NOTE |
| FOR IT. IF IT STANDS FOR GRAVITY DRAIN, WOULD YOU |
| PLEASE PROVIDE DETAIL OR MANUFACTURES SPECIFICATION AND |
| CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. THIS IS A MULTI-FAMILY DWELLING, AND WATER USERS |
| WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW |
| ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF |
| HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE |
| BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER |
| THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND |
| THEIR CONNECTION CONTROL PROGRAM. A NOTE ON PLANS FOR A |
| SEPARATE PERMIT FOR BACKFLOW WILL BE FINE. |
| |
| 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |