Plan Review Notes For Permit 21081320 |
Permit Number |
21081320 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-08-28 07:35:40 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21081320 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR BOTH THE | | CABANA AND THE MAIN HOUSE. FBC EC 101.5.1.1.2 | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS FOR BOTH THE CABANA AND THE MAIN HOUSE. | | FBC EC R403.7 | | | | 3) THE CABANA WILL REQUIRE A SEPARATE PERMIT. | | | | 4) PLEASE PROVIDE A DETAIL OF THE CONDENSING UNITS TIE | | DOWN. FBC RES M1307.2 | | | | 5) PLEASE SHOW THE CONDENSATION PIPING AND THE | | TERMINATION LOCATION. FBC RES M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|