Plan Review Notes For Permit 21081320 |
Permit Number |
21081320 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-09-07 13:03:45 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | RISER DIAGRAM | | | | ALL PANELS HAVE 400A BUSS? | | | | PANEL LDP3 NEEDS A GROUNDING ELECTRODE SYSTEM | | INSTALLED. 250.32 | | | | MDP SHOWS 2 CAR CHARGERS THAT ARE NOT SHOWN ON PLAN. | | | | LDP4 NOT SHOWN ON PLANS AND DOES NOT HAVE A PANEL | | SCHEDULE | | | | NOT SMOKE ALARMS SHOWN ON PLANS FBC R314,315 | | | | LDP1, LDP2, LDP3, P ALL SHOWN AS TWO POLE 20A BREAKERS. | | 215.5 | | | | CABANA GFCI PROTECTION REQUIRED WITHIN 6' OF THE SINK | | ON FIRST FLOOR. 210.8 | | | | CABANA SMOKE ALARMS NEEDED ON FIRST AND SECOND FLOORS. | | FBC R314 | | | | |
|