2021-09-07 10:19:47 | COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST. |
| PLEASE COMPLY. |
| |
| RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21081294 |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| 1- FLAT ROOF NOA 18-0919.07 SUBMITTED: SELECTED |
| ASSEMBLIES FOR THE INSULATED AND NON-INSULATED ROOF |
| SYSTEMS DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF |
| ZONES. PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS |
| FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA. |
| NEED THE CALCULATIONS TO MEET THE DESIGN PRESSURES |
| REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "D". |
| |
| 2- ROOFING UNDERLAYMENT |
| PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE |
| NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. |
| SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001 |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |