2021-11-18 16:36:17 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT- 21081267 |
| 11/18/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 6TH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 6TH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE 6TH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 6TH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS FOR THE MAIN POOL- DENIED. FAILED |
| COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW WITH |
| ADDITIONAL NOTES IN CAP LETTERS. |
| |
| 1) FAIILED. PLEASE PROVIDE A LIST OF REQUIRED SEPARATE |
| PERMITS ON THE PLAN INCLUDING- |
| ON SITE PLUMBING FOR WATER SUPPLY AND WASTE-WATER |
| DISPOSAL. |
| BACKFLOW PREVENTER FOR THE WATER SUPPLY TO THE POOL. |
| AUTO FILL INSTALLATION. |
| RESTROOM FACILITY AND PLUMBING AND FIXTURE |
| INSTALLATIONS. |
| POOL SHOWER AND HOSE BIB PLUMBING AND FIXTURE |
| INSTALLATIONS. |
| PAVILION AND EQUIPMENT ENCLOSURE CONSTRUCTION. |
| POOL FENCE |
| PAVER DECK |
| |
| 5) FAILED. SHEET 1: THE DISCHARGE WATER FROM THE POOL |
| SHALL NOT DRAIN INTO THE CITY SANITARY SYSTEM- SECTION |
| 454.1.6.5.15 & SEC. 90-126(5) WPB CODE OF ORDINANCES. |
| PLEASE REVISE THE PLANS TO SHOW AN APPROVED PLACE OF |
| DISPOSAL. THE DISCHARGE WATER IS ALSO SHOWN TO BE |
| DRAINING INTO THE STORM DRAIN SYSTEM IN THE WASTE |
| DETAIL ON SHEET 6. PLEASE NOTE THAT THE CITY OF WPB |
| UTILITIES DEPT. PROHIBITS POOL WASTE-WATER FROM |
| DRAINING INTO THE STORM DRAIN SYSTEM UNLESS THE WATER |
| HAS BEEN DECHLORINATED. THE ENGINEER OF RECORD SHALL |
| PROVIDE A PROCEDURE AND EQUIPMENT SPECIFICATIONS. IN |
| RESPONSE ONE OF THE TWO RESPONSE NARRATIVES INDICATES |
| ALL WATER TO BE DE-CHLORINATED AND ROUTED TO THE STORM. |
| THE SECOND NARRATIVE INDICATES A DE-CHLORINATOR HAS |
| BEEN PROVIDED. |
| |
| A) PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| DE-CHLORINATOR. |
| |
| B) PLEASE CONTACT THE CHRIS JACKSON, ENVIRONMENTAL |
| COMPLIANCE SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, |
| 561-822-2062 OR [email protected] FOR FURTHER |
| DIRECTION. |
| |
| C) PLEASE REMOVE ALL DETAILS AND NOTES FROM THE PLAN |
| INDICATING POOL WASTE WATER DRAINING INTO THE SANITARY, |
| AND ADD NOTES TO INDICATE ONLY DE-CHLORINATED WATER TO |
| DRAIN INTO THE STORM SYSTEM- SEE SHEETS PPP-2, P0-1, |
| P0-3, P0-6. |
| |
| 13) FAILED. SHEET 2: PROVIDE TOTAL DYNAMIC HEAD |
| CALCULATIONS AND THE PUMP CURVE FROM THE MANUFACTURER- |
| SECTION 454.1.6.5.4 FBC B. TDH CALCS AND PUMP CURVE NOT |
| PROVIDED. |
| |
| 16) FAILED. SHEETS 4 & 6: PLEASE PROVIDE THE DIMENSIONS |
| OF THE GUTTERS IN COMPLIANCE WITH SECTION |
| 454.1.6.5.3.1.1 FBC B. NOT PROVIDED. |
| |
| 20) PLEASE SHOW COMPLIANCE WITH THE FOLLOWING CODE |
| SECTIONS FROM THE FBC EC: |
| FAILED. C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL |
| HEATERS SHALL BE CONTROLLED BY A READILY ACCESSIBLE |
| ON-OFF SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, |
| MOUNTED ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO |
| AND WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF |
| SUCH SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER |
| THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A |
| CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED |
| HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING |
| IGNITION PILOTS. HEATER SPECS WERE NOT PROVIDED AND |
| SWITCH LOCATION NOT SHOWN. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |