Plan Review Notes
Plan Review Notes For Permit 21081225
Permit Number 21081225
Review Stop B
Sequence Number 2
Notes
Date Text
2021-09-15 14:17:59****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 3103.1.1, SANITARY REQUIREMENTS, PROVIDE,
 LOCATION ON SITE-PLAN, ACCESSIBLE RESTROOMS WITHIN 500'
 OF TENT LOCATIONS.
  
 FBC B 107.2.1, **ADDITIONAL REQUIREMENTS
 FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN
 OF 30 FEET OR GREATER IN ANY DIRECTION:
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
 PLEASE ADJUST ENGINEER'S LETTER TO STATE THAT: THIS
 TENT SHALL BE REMOVED IF WINDS ARE EXPECTEDTO
 EXCEED 30 M.P.H.
 THERE WILL BE NO EXCEPTION TO THE ABOVE REQUIREMENT FOR
 TENTS WITH A SPAN IN ANY
 DIRECTION OF 40? OR MORE.
  
 _______________________________________________________
 ________