Plan Review Notes
Plan Review Notes For Permit 21081187
Permit Number 21081187
Review Stop G
Sequence Number 1
Notes
Date Text
2021-09-17 16:22:231ST REVIEW FBC-2020 RES. BUILDING.
 PERMIT- 21081187
 9/17/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS RISER DRAWING INDICATES TABLE 402.4(32) FOR
 LOW PRESSURE CSST HOWEVER NO CSST IS SHOWN ON RISER-
 SECTION G2413.4 FBC RES.
  
 2) PLEASE PROVIDE COMPLETE REGULATOR SPECS FOR THE 1ST
 AND 2ND STAGE REGULATORS- SECTION G2421.2 FBC RES. MARK
 OR HIGHLIGHT THE SELECTED MODEL FOR EACH, AND THE INPUT
 AND OUTPUT PIPE SIZES AND PRESSURES.
  
 3) PROVIDE CLEARER, LEGIBLE TANK ANCHORING
 SPECIFICATIONS AND DETAILS- SECTION 107.2.1 WPB. PLEASE
 NOTE THAT DETAILS PREPARED BY A FL. LICENSED ENGINEER
 THAT ARE TRANSMITTED ELECTRONICALLY SHALL BE DIGITALLY
 SIGNED AND SEALED, OR IF SUBMITTED IN PAPER FORM, SHALL
 THE RAISED OR INK SEAL AND WET SIGNATURE OF THE
 ENGINEER- -FL. STATUTE 471.025 AND SECTION 61G15-23.005
 FLORIDA ADMINISTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  