2022-06-30 11:28:26PASSED ELECTRIC REVIEW WITH THE PROVISO TO ENSURE
 COMPLIANCE WITH THE BELOW COMMENTS.MP
  
 ELECTRICAL REVIEW FAILED
  
 1) PLEASE PROVIDE LOAD CALCULATIONS FOR DOCK PANEL THAT
 CORRECTLY STATE THE LOADS BEING SERVED. I.E. SHORE
 POWER IS LISTED AS 30 AMP, DRAWING DETAILS 50-AMP. NO
 BOAT LIFTS ARE DETAILED. NEC 215.5 PANEL SCHEDULE HAS
 BEEN REVISED TO SHOW A 50-AMP SHORE POWER PEDESTAL,
 HOWEVER BOATLIFT CIRCUITS ARE STILL NOT LISTED IN THE
 SCHEDULE AND LOAD CALCULATIONS UPDATED.
 NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE
 AUTHORITY HAVING
 JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS SHALL BE
 PROVIDED
 PRIOR TO THE INSTALLATION OF THE FEEDERS. SUCH A
 DIAGRAM SHALL
 SHOW THE AREA IN SQUARE FEET OF THE BUILDING OR OTHER
 STRUCTURE
 SUPPLIED BY EACH FEEDER, THE TOTAL CALCULATED LOAD
 BEFORE APPLYING
 DEMAND FACTORS, THE DEMAND FACTORS USED, THE CALCULATED
 -------------------------------------------------------
 -------------------------------------------------
 2) PLEASE DETAIL GROUND FAULT PROTECTION AS REQUIRED BY
 NEC 555.3 AND 210.8(C) THERE IS STILL NO INDICATION ON
 ANY PLANS OR SCHEDULES DETAILING THE REQUIRED GFP AS
 REQUIRED
 NEC 210.8(C) BOAT HOISTS. GFCI PROTECTION SHALL BE
 PROVIDED FOR OUTLETS
 NOT EXCEEDING 240 VOLTS THAT SUPPLY BOAT HOISTS
 INSTALLED IN DWELLING
 UNIT LOCATIONS.
 NEC 555.3 GROUND-FAULT PROTECTION. THE OVERCURRENT
 PROTECTIVE
 DEVICES THAT SUPPLY THE MARINA, BOATYARDS, AND
 COMMERCIAL AND
 NONCOMMERCIAL DOCKING FACILITIES SHALL HAVE
 GROUND-FAULT PROTECTION
 NOT EXCEEDING 30 MA.
 -------------------------------------------------------
 --------------------------------------------------
 3) PLEASE DETAIL ELECTRIC CONNECTIONS ARE 12? ABOVE
 ELECTRICAL DATUM PLANE AS DETAILED BY NEC 555.2 AND
 555.9. ALTHOUGH PLAN LABELED BOAT LIFT SECTION DOES NOT
 DETAIL THESE MEASUREMENTS, ONE MIGHT ASSUME THE
 ELECTRICAL CONNECTIONS SHOULD BE IN COMPLIANCE
 555.2 DEFINITIONS.
 ELECTRICAL DATUM PLANE. THE ELECTRICAL DATUM PLANE IS
 DEFINED
 AS FOLLOWS:
 (1) IN LAND AREAS SUBJECT TO TIDAL FLUCTUATION, THE
 ELECTRICAL
 DATUM PLANE IS A HORIZONTAL PLANE 606 MM (2 FT) ABOVE
 THE HIGHEST TIDE LEVEL FOR THE AREA OCCURRING UNDER
 NORMAL
 CIRCUMSTANCES, THAT IS, HIGHEST HIGH TIDE.
 555.9 ELECTRICAL CONNECTIONS. ELECTRICAL CONNECTIONS
 SHALL BE
 LOCATED AT LEAST 305 MM (12 IN.) ABOVE THE DECK OF A
 FLOATING PIER.
 CONDUCTOR SPLICES, WITHIN APPROVED JUNCTION BOXES,
 UTILIZING
 SEALED WIRE CONNECTOR SYSTEMS LISTED AND IDENTIFIED FOR
 SUBMERSION
 SHALL BE PERMITTED WHERE LOCATED ABOVE THE WATERLINE
 BUT
 BELOW THE ELECTRICAL DATUM PLANE FOR FLOATING PIERS.
 ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST
 305 MM
 (12 IN.) ABOVE THE DECK OF A FIXED PIER BUT NOT BELOW
 THE ELECTRICAL
 DATUM PLANE.
 -------------------------------------------------------
 -----------------------------------------------
 4) PLEASE DETAIL SHOCK HAZARD SIGNAGE AS REQUIRED BY
 NEC 555.24. SHOCK HAZARD SIGN HAS BEEN PROVIDED IN THE
 SUPPORTING DOCS FOLDER
 -------------------------------------------------------
 -------------------------------------------------------
 -----------------------
 5) PLEASE PROVIDE CONDUCTOR SIZES AND OVERCURRENT
 PROTECTION INSTALLED TO DOCK EQUIPMENT TO DETAIL
 COMPLIANCE WITH NEC 210.19(1) AND NEC 240.4. NO
 CONDUCTOR SIZES OR OVERCURRENT PROTECTION IS SHOWN ON
 ANY PLAN OR SCHEDULE FOR BOAT LIFTS
 210.19 CONDUCTORS ? MINIMUM AMPACITY AND SIZE.
 (A) BRANCH CIRCUITS NOT MORE THAN 600 VOLTS.
 (1) GENERAL. BRANCH-CIRCUIT CONDUCTORS SHALL HAVE AN
 AMPACITY
 NOT LESS THAN THE MAXIMUM LOAD TO BE SERVED. CONDUCTORS
 SHALL BE
 SIZED TO CARRY NOT LESS THAN THE LARGER OF
 210.19(A)(1)(A) OR (B).
 -------------------------------------------------------
 ---------------------------------------------------
 6) PLEASE DETAIL CONDUCTORS/FEEDERS ARE SIZED FOR
 MAXIMUM VOLTAGE DROP AS REQUIRED PER 2020 FBC ENERGY
 CONSERVATION C405.5.3. NO SUPPORTING DOCUMENTATION HAS
 BEEN PROVIDED TO SHOW COMPLIANCE
 C405.5 ELECTRICAL POWER (MANDATORY).
 C405.5.3 VOLTAGE DROP. THE CONDUCTORS FOR FEEDERS AND
 BRANCH CIRCUITS COMBINED SHALL BE SIZED FOR A MAXIMUM
 OF
 5 PERCENT VOLTAGE DROP TOTAL.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
  
  