2022-04-20 10:57:58 | ELECTRIC REVIEW FAILED |
| 1) PLEASE PROVIDE LOAD CALCULATIONS FOR DOCK PANEL THAT |
| CORRECTLY STATE THE LOADS BEING SERVED. I.E. SHORE |
| POWER IS LISTED AS 30 AMP, DRAWING DETAILS 50-AMP. NO |
| BOAT LIFTS ARE DETAILED. NEC 215.5 |
| 2) PLEASE DETAIL GROUND FAULT PROTECTION AS REQUIRED BY |
| NEC 555.3 AND 210.8(C) |
| 3) PLEASE DETAIL ELECTRIC CONNECTIONS ARE 12? ABOVE |
| ELECTRICAL DATUM PLANE AS DETAILED BY NEC 555.2 AND |
| 555.9 |
| 4) PLEASE DETAIL SHOCK HAZARD SIGNAGE AS REQUIRED BY |
| NEC 555.24 |
| 5) PLEASE PROVIDE CONDUCTOR SIZES AND OVERCURRENT |
| PROTECTION INSTALLED TO DOCK EQUIPMENT TO DETAIL |
| COMPLIANCE WITH NEC 210.19(1) AND NEC 240.4 |
| 6) PLEASE DETAIL CONDUCTORS/FEEDERS ARE SIZED FOR |
| MAXIMUM VOLTAGE DROP AS REQUIRED PER 2020 FBC ENERGY |
| CONSERVATION C405.5.3 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |