2022-01-18 17:34:12PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 NEW COMMENTS:
  
 1) THE MEAN ROOF HEIGHT OF THE BUILDING IS USED TO
 DETERMINE THE COMPONENT AND CLADDING PRESSURES. THIS IS
 A TEN STORY BUILDING (APPROXIMATELY 120' IN HEIGHT) THE
 MRH WILL BE GREATER THAN 60 FEET. THE WIND LOAD
 ENGINEERING IS FOR BUILDINGS WITH MEAN ROOF HEIGHTS OF
 60 FEET OR LESS. PLEASE CORRECT. FBC 1609
  
 2) THE EXPOSURE CATEGORY FOR THIS BUILDING IS EXPOSURE
 D. THE SIGNED AND SEALED DRAWING FROM TOMAS PONCE PE
 HAS THE WINDLOAD CRITERIA FOR EXPOSURE C AND IS FOR
 MEAN ROOF HEIGHTS OF 60' OR LESS. PLEASE CORRECT THE
 DATUM. FBC 1609.1
  