2021-09-21 16:56:53 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21081110 |
| ADD: 7106 S. DIXIE HWY. |
| CONT: CAMPBELL GENERAL CONTRACTING |
| TEL: 772-486-3764 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. SEPT. 21ST/2021 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. THE PERMIT APPLICATION DOES NOT |
| INDICATE IF THIS STRUCTURE IS TO BE CONSIDERED |
| TEMPORARY IN NATURE OR TO BE CONSIDERED A PERMANENT |
| STRUCTURE. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| SECTION 108.1. THE BUILDING OFFICIAL IS AUTHORIZED TO |
| ISSUE A PERMIT FOR TEMPORARY STRUCTURES AND TEMPORARY |
| USES. SUCH PERMITS SHALL BE LIMITED AS TO TIME OF |
| SERVICE BUT SHALL NOT BE PERMITTED FOR MORE THAN 6 |
| MONTHS. THE BUILDING OFFICIAL IS AUTHORIZED TO GRANT |
| EXTENSIONS FOR DEMONSTRATED CAUSE. PLEASE PROVIDE WHAT |
| THE USAGE WILL BE (OCCUPANCY TYPE). |
| |
| 108.2 CONFORMANCE. TEMPORARY STRUCTURES AND USES SHALL |
| CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS |
| OF EGRESS, ACCESSIBILITY, LIGHT. VENTILATION AND |
| SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO |
| ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE. |
| |
| 2) 2ND REQUEST. IF THE STRUCTURE IS GOING TO BE |
| PERMANENT THEN THE STRUCTURE WILL NEED TO SHOW |
| COMPLIANCE WITH 108.2 CONFORMANCE. PERMANENT STRUCTURES |
| AND USES SHALL CONFORM TO THE STRUCTURAL STRENGTH, FIRE |
| SAFETY, MEANS OF EGRESS, ACCESSIBILITY, LIGHT. |
| VENTILATION AND SANITARY REQUIREMENTS OF THIS CODE AS |
| NECESSARY TO ENSURE PUBLIC HEALTH, SAFETY AND GENERAL |
| WELFARE. |
| |
| 3) A STRUCTURAL ENGINEER WILL NEED TO ENGINEER AND OR |
| CALCULATE ANCHORAGE OF THIS UNIT IN CONFORMANCE WITH |
| THE 2020 FBC-BUILDING SECTION 1604.8 ANCHORAGE. THE |
| SHEET S-2 NOTES: |
| |
| |
| 3A) NOTE 3 GROUND ANCHORS ARE TO HAVE A MINIMUM TENSION |
| CAPACITY OF 2,250 LBS, CONTRACTOR TO MANUFACTURERS |
| SPECS. |
| |
| 3B) GALVANIZED WIRE ROPE IS TO HAVE A MINIMUM TENSION |
| CAPACITY OF 2,250 LBS. THE DESIGNER OF RECORD HAS NOT |
| INDICATED THE SIZE OF WIRE ROPE NOR THE TENSILE |
| STRENGTH. |
| |
| 3C) THE DESIGNER OF RECORD HAS NOT IDENTIFIED THE TYPE |
| OF FASTENERS AT EACH END OF THE WIRE ROPE, NOR THE SIZE |
| AND CAPACITY OF FASTENERS, ARE MULTIPLE FASTENERS |
| REQUIRED AT EACH END? |
| |
| 1ST REVIEW COMMENTS. BUILDINGS AND OTHER STRUCTURE, AND |
| PORTIONS THEREOF, SHALL BE PROVIDED WITH ANCHORAGE IN |
| ACCORDANCE WITH SECTIONS 1604.8.1 THROUGH 1604.8.3 AS |
| APPLICABLE. PERMANENT BUILDINGS HAVE FOUNDATIONS, SEE |
| 1809.4 DEPTH AND WIDTH OF FOUNDATIONS. |
| |
| 4) THE ENGINEER WILL HAVE TO ENGINEER THE ANCHORAGE TO |
| THE PROPER WIND ZONE TO KEEP THE STRUCTURE FROM SLIDING |
| AND OR TIPPING OVER. 2020 FBC-BUILDING CODE 1609.1.1 |
| DETERMINATION OF WIND LOADS. |
| |
| 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE |
| WORKING FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |