2022-04-08 14:47:28PLAN REVIEW COMMENTS
  
 7 TH REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
  
 NOTE: IT IS ACKNOWLEDGED BY THE CITY BUILDING DIVISION
 THAT THESE ROLL-UP STORM SHUTTERS PROPOSED FOR THE ROOF
 TOP GAZEBO ARE NOT REQUIRED TO BE INSTALLED BY THE
 FLORIDA BUILDING CODE.
  
 1) NOT RESOLVED. [ SUBMIT NEW ENGINEERING FOR OPENING
 DESIGN PRESSURES. SEE COMMENT #2. ] PROVIDE A LETTER
 FROM A FLORIDA LICENSED ENGINEER AFFIRMING THAT THE
 INSTALLATION OF THESE ROLL-UP STORM SHUTTERS WILL NOT
 HAVE AN ADVERSE EFFECT ON THE HOST STRUCTURE WHEN IN
 USE DURING A WIND EVENT. FBC 1604.2 & 107.2.1
  
 2) NOT RESOLVED. [ THE DESIGN PRESSURES IN THE LATEST
 INSTALLATION SCHEDULE AND THE UPDATED DESIGN PRESSURES
 FROM STORM SMART DO NOT CORRESPOND WITH THE OPENING
 DESIGN PRESSURES FROM THE PROFESSIONAL ENGINEER
 (ENGINEERING EXPRESS). BECAUSE THIS IS A HIGHRISE
 BUILDING SIGNED AND SEALED ENGINEERING FROM A FLORIDA
 LICENSED P.E. FOR THE WINDLOAD DATA AND OPENING DESIGN
 PRESSURES IS REQUIRED. ] PLEASE HAVE THE ENGINEER
 EXPLAIN THE SUBSTANTIAL PRESSURE DIFFERENCE BETWEEN THE
 DESIGN PRESSURES FOR OPENING #1 AND THE OTHER OPENINGS.
 ESPECIALLY OPENING #5 WHICH IS IN THE SAME WALL ZONE
 AND IS 134.5 SQFT COMPARED TO 202.5 SQFT. FBC 1604.2
  
 3) RESOLVED. A NEW INSTALLATION SCHEDULE WAS SUBMITTED.
 NOTE: THE OPENING SIZES AND DESIGN PRESSURES WILL HAVE
 TO BE CONSISTENT WITH THE ENGINEERING. FBC AMENDMENTS
 107.2.1
  
 4) RESOLVED. OPENIING SIZE WAS CORRECTED.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  