2022-04-08 14:47:28 | PLAN REVIEW COMMENTS |
| |
| 7 TH REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| |
| NOTE: IT IS ACKNOWLEDGED BY THE CITY BUILDING DIVISION |
| THAT THESE ROLL-UP STORM SHUTTERS PROPOSED FOR THE ROOF |
| TOP GAZEBO ARE NOT REQUIRED TO BE INSTALLED BY THE |
| FLORIDA BUILDING CODE. |
| |
| 1) NOT RESOLVED. [ SUBMIT NEW ENGINEERING FOR OPENING |
| DESIGN PRESSURES. SEE COMMENT #2. ] PROVIDE A LETTER |
| FROM A FLORIDA LICENSED ENGINEER AFFIRMING THAT THE |
| INSTALLATION OF THESE ROLL-UP STORM SHUTTERS WILL NOT |
| HAVE AN ADVERSE EFFECT ON THE HOST STRUCTURE WHEN IN |
| USE DURING A WIND EVENT. FBC 1604.2 & 107.2.1 |
| |
| 2) NOT RESOLVED. [ THE DESIGN PRESSURES IN THE LATEST |
| INSTALLATION SCHEDULE AND THE UPDATED DESIGN PRESSURES |
| FROM STORM SMART DO NOT CORRESPOND WITH THE OPENING |
| DESIGN PRESSURES FROM THE PROFESSIONAL ENGINEER |
| (ENGINEERING EXPRESS). BECAUSE THIS IS A HIGHRISE |
| BUILDING SIGNED AND SEALED ENGINEERING FROM A FLORIDA |
| LICENSED P.E. FOR THE WINDLOAD DATA AND OPENING DESIGN |
| PRESSURES IS REQUIRED. ] PLEASE HAVE THE ENGINEER |
| EXPLAIN THE SUBSTANTIAL PRESSURE DIFFERENCE BETWEEN THE |
| DESIGN PRESSURES FOR OPENING #1 AND THE OTHER OPENINGS. |
| ESPECIALLY OPENING #5 WHICH IS IN THE SAME WALL ZONE |
| AND IS 134.5 SQFT COMPARED TO 202.5 SQFT. FBC 1604.2 |
| |
| 3) RESOLVED. A NEW INSTALLATION SCHEDULE WAS SUBMITTED. |
| NOTE: THE OPENING SIZES AND DESIGN PRESSURES WILL HAVE |
| TO BE CONSISTENT WITH THE ENGINEERING. FBC AMENDMENTS |
| 107.2.1 |
| |
| 4) RESOLVED. OPENIING SIZE WAS CORRECTED. |
| |
| 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |