Plan Review Notes
Plan Review Notes For Permit 21081109
Permit Number 21081109
Review Stop B
Sequence Number 6
Notes
Date Text
2022-04-04 11:27:02PLAN REVIEW COMMENTS
  
 6 TH REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
  
 NOTE: IT IS ACKNOWLEDGED BY THE CITY BUILDING DIVISION
 THAT THESE ROLL-UP STORM SHUTTERS PROPOSED FOR THE ROOF
 TOP GAZEBO ARE NOT REQUIRED TO BE INSTALLED BY THE
 FLORIDA BUILDING CODE.
  
 1) PROVIDE A LETTER FROM A FLORIDA LICENSED ENGINEER
 AFFIRMING THAT THE INSTALLATION OF THESE ROLL-UP STORM
 SHUTTERS WILL NOT HAVE AN ADVERSE EFFECT ON THE HOST
 STRUCTURE WHEN IN USE DURING A WIND EVENT. FBC 1604.2 &
 107.2.1
  
 2) PLEASE HAVE THE ENGINEER EXPLAIN THE SUBSTANTIAL
 PRESSURE DIFFERENCE BETWEEN THE DESIGN PRESSURES FOR
 OPENING #1 AND THE OTHER OPENINGS. ESPECIALLY OPENING
 #5 WHICH IS IN THE SAME WALL ZONE AND IS 134.5 SQFT
 COMPARED TO 202.5 SQFT. FBC 1604.2
  
 3) SUBMIT A CORRECTED HURRICANE SHUTTER INSTALLATION
 SCHEDULE. FBC 107.2.1
  
 4) ON SHEET 9 OF 29 OF THE MULLION PRODUCT APPROVAL
 (FL13068-R5), THE DESIGN PRESSURE OF 105 PSF IS CIRCLED
 FOR THE AVERAGE SPAN WIDTH OF UP TO 132" AND A MULLION
 LENGTH UP TO 144". I BELIEVE THAT THE OPENING IN
 QUESTION IS 197" WIDE AND 148" IN HEIGHT (BASED ON
 INFORMATION THAT WAS PREVIOUSLY PROVIDED). THE REQUIRED
 LENGTH FOR THE MULLION WOULD EXCEED THE 144" MULLION
 LENGTH ALLOWED BY THE PRODUCT APPROVAL. PLEASE CLARIFY.
 FBC 107.2.1 & 1604.2
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  