2022-02-14 10:48:52PLAN REVIEW COMMENTS
  
 5 TH REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - THE PROPOSED SCREEN FABRIC IMPACT
 PROTECTION DEVICE HAS A MAXIMUM DESIGN PRESSURES OF +/-
 60 PSF WHICH IS LESS THAN THE REQUIRED OPENING
 PRESSURES. WE ACKNOWLEDGE THAT THE ROLL UP AND FABRIC
 SHUTTERS ARE NOT BEING INSTALLED TO PROVIDE IMPACT
 PROTECTION. OUR CONCERN IS THAT THE DEVICES REMAIN
 INTACT AND NOT BECOME DETACHED DURING A WIND EVENT. THE
 ROLL UP SHUTTERS ARE DESIGNED TO BE INSTALLED ON AN
 ENCLOSED BUILDING AND THE FABRIC PANEL WILL ALLOW THE
 WIND INTO THE INTERIOR OF THE GAZEBO WHICH WILL
 INCREASE THE PRESSURE ON THE INTERNAL SIDE OF THE ROLL
 UP SHUTTERS. THE INTERNAL PRESSURE WILL BE GREATER THAN
 THE CONFIGURATION TESTED FOR THE PRODUCT APPROVAL. YOU
 MAY WISH TO LOOK AT OTHER OPTIONS, POSSIBLY ROLL UP
 GARAGE DOORS.
  
  
 PREVIOUS REVIEW COMMENTS BELOW FOR REFERENCE
 PLAN REVIEW COMMENTS
  
 4 TH REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 COMMENTS FROM THE 3RD REVIEW WERE NOT ADDRESSED.
  
 NOTE: IT IS ACKNOWLEDGED BY THE CITY BUILDING DIVISION
 THAT THESE ROLL-UP STORM SHUTTERS PROPOSED FOR THE ROOF
 TOP GAZEBO ARE NOT REQUIRED TO BE INSTALLED BY THE
 FLORIDA BUILDING CODE.
  
 1) PROVIDE A LETTER FROM A FLORIDA LICENSED ENGINEER
 AFFIRMING THAT THE INSTALLATION OF THESE ROLL-UP STORM
 SHUTTERS WILL NOT HAVE AN ADVERSE EFFECT ON THE HOST
 STRUCTURE WHEN IN USE DURING A WIND EVENT. FBC
 107.2.1.2
  
 2) PLEASE HAVE THE ENGINEER EXPLAIN THE SUBSTANTIAL
 PRESSURE DIFFERENCE BETWEEN THE DESIGN PRESSURES FOR
 OPENING #1 AND THE OTHER OPENINGS. ESPECIALLY OPENING
 #5 WHICH IS IN THE SAME WALL ZONE AND IS 134.5 SQFT
 COMPARED TO 202.5 SQFT. FBC 107.2.1.2
  
 3) THE CUSTOM MOUNT DETAIL FOR OPENING #1 SHOWS ADDING
 AN ALUMINUM ANGLE TO THE END RETENTION TRACK. I BELIEVE
 THAT YOU INTEND THIS TO INCREASE THE DESIGN PRESSURE OF
 THE ROLL-UP SHUTTERS. THE ENGINEER WILL NEED TO PROVIDE
 A RATIONAL ANALYSIS THAT EXPLAINS HOW THIS WILL
 INCREASE THE DESIGN PRESSURES OF THE PRODUCT. THE
 ENGINEER WILL NEED TO PROVIDE A COPY OF THE TEST REPORT
 FOR THE ROLL-UP SHUTTERS THAT INDICATES THE MODE OF
 FAILURE. THE REPORT NEEDS TO SHOW WHICH COMPONENT OF
 THE ROLL-UP FAILED. IF IT IS THE SLATS THAT FAILED WHEN
 TESTED, REINFORCING THE RETENTION TRACK WILL NOT
 INCREASE THE PRODUCT'S DESIGN PRESSURE. FBC 107.2.1
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  