Plan Review Notes
Plan Review Notes For Permit 21081109
Permit Number 21081109
Review Stop B
Sequence Number 4
Notes
Date Text
2021-12-01 13:20:25PLAN
 REVIEW COMMENTS
  
 4TH REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 COMMENTS FROM THE 3RD REVIEW WERE NOT ADDRESSED.
  
 NOTE: IT IS ACKNOWLEDGED BY THE CITY BUILDING DIVISION
 THAT THESE ROLL-UP STORM SHUTTERS PROPOSED FOR THE ROOF
 TOP GAZEBO ARE NOT REQUIRED TO BE INSTALLED BY THE
 FLORIDA BUILDING CODE.
  
 1) PROVIDE A LETTER FROM A FLORIDA LICENSED ENGINEER
 AFFIRMING THAT THE INSTALLATION OF THESE ROLL-UP STORM
 SHUTTERS WILL NOT HAVE AN ADVERSE EFFECT ON THE HOST
 STRUCTURE WHEN IN USE DURING A WIND EVENT. FBC
 107.2.1.2
  
 2) PLEASE HAVE THE ENGINEER EXPLAIN THE SUBSTANTIAL
 PRESSURE DIFFERENCE BETWEEN THE DESIGN PRESSURES FOR
 OPENING #1 AND THE OTHER OPENINGS. ESPECIALLY OPENING
 #5 WHICH IS IN THE SAME WALL ZONE AND IS 134.5 SQFT
 COMPARED TO 202.5 SQFT. FBC 107.2.1.2
  
 3) THE CUSTOM MOUNT DETAIL FOR OPENING #1 SHOWS ADDING
 AN ALUMINUM ANGLE TO THE END RETENTION TRACK. I BELIEVE
 THAT YOU INTEND THIS TO INCREASE THE DESIGN PRESSURE OF
 THE ROLL-UP SHUTTERS. THE ENGINEER WILL NEED TO PROVIDE
 A RATIONAL ANALYSIS THAT EXPLAINS HOW THIS WILL
 INCREASE THE DESIGN PRESSURES OF THE PRODUCT. THE
 ENGINEER WILL NEED TO PROVIDE A COPY OF THE TEST REPORT
 FOR THE ROLL-UP SHUTTERS THAT INDICATES THE MODE OF
 FAILURE. THE REPORT NEEDS TO SHOW WHICH COMPONENT OF
 THE ROLL-UP FAILED. IF IT IS THE SLATS THAT FAILED WHEN
 TESTED, REINFORCING THE RETENTION TRACK WILL NOT
 INCREASE THE PRODUCT'S DESIGN PRESSURE. FBC 107.2.1
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.