Plan Review Notes For Permit 21081097 |
Permit Number |
21081097 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-13 16:59:26 | FAILED | | | | 1) THE LAYOUT OF THE PROPANE PAD AND THE PARKING | | ADJACENT TO IT ON THE PROPANE KEY PLAN, SHEET FP.110 DO | | NOT MATCH THE APPROVED SITE PLAN. ALL PLANS MUST SHOW | | THE SAME CONDITIONS. STAFF HAS NOTED THE FOLLOWING | | ABOUT SHEET FP.110: | | | | A. THE CURBING DOES NOT MATCH THE APPROVED PLANS. | | B. THE REQUIRED LANDSCAPE SCREENING AREA ON THE SOUTH | | AND WEST SIDES OF THE ENCLOSURE ARE MISSING. | | C. NON-COMPLIANT ADA PARKING SPACE. NOTE: EVEN IF THE | | PARKING SPACE IS NOT AN ADA SPACE, THE CONFIGURATION | | WOULD RESULT IN A LOSS OF A PARKING SPACE ON THE SITE. | | AN ADA SPACE AND THE REQUIRED AISLE REMOVE ADDITIONAL | | PARKING SPACES. | | | | 2) THE PROPANE TANK ENCLOSURE WALL REQUIRES A SEPARATE | | PERMIT, WITH PLANS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | [email protected] | | | | |
|