2021-09-22 12:22:33 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT:21081053 |
| ADD: 5200 N FLAGLER DR. # 502 |
| CONT: PAUL?S MAINTENANCE INC. |
| TEL: 561-798-5722 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. SEPT. 22ND/ 2021 |
| ACTION: DENIED |
| 1) THE CONTRACTOR DRAWN PLANS DOES NOT INDICATE THE |
| AUTHOR OF THE PLANS. CERTIFICATION BY CONTRACTOR. |
| 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED / |
| DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES |
| AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| LICENSED IN AND PLANS DRAWN. |
| 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| AND PLANS DRAWN. |
| |
| 2) THE FLOOR PLAN INDICATES THE REMOVAL OF A TUB AND |
| INSTALLATION OF A NEW SHOWER. IT IS NOT CLEAR IF THE |
| EXISTING DRAIN LOCATION IS TO BE REUSED OR A NEW HOLE |
| CORED THROUGH THE SLAB. POST TENSION SLAB/ NEW HOLES. |
| THE PLAN IS SILENT AS IF THE LOCATION OF THE EXISTING |
| TUB DRAIN IS GOING TO BE REUSED IN THE SAME LOCATION. |
| IF NOT, THEN THE FLOOR SLAB WILL NEED TO BE X-RAYED TO |
| FIND THE POST TENSION CHORD LOCATIONS. 107.2.1.2. |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE |
| FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE |
| WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| PENETRATED. |
| |
| 4) THE FLOOR PLAN DOES NOT SHOW COMPLIANCE WITH THE |
| 2020 FBC-BUILDING SECTIONS: |
| |
| 4A) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS |
| A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| THE MANUFACTURE?S RECOMMENDATIONS. |
| |
| 4B) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| |
| 5) THE FLOOR PLAN NOR PAN DETAIL DOES NOT MAKE IT CLEAR |
| AS IF THE BATHROOM FLOOR IS BEING REPLACED, IF SO SHOW |
| COMPLIANCE WITH THE 2020 FBC-BUILDING SECTIONS: |
| FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE |
| HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO |
| THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 5A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 5B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 5C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE |
| WORKING FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |