Date |
Text |
2021-08-24 16:21:48 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 21080885 7310 GEORGIA AVE # 1 |
| MASTER PERMIT 19120571 |
| |
| 1ST REVIEW |
| |
| GAS COMMENTS: DENIED |
| |
| 1.PER WPB FBC 107.2.1, PROVIDE GAS FLOOR PLAN SHOWING |
| LOCATION OF RELOCATED METER/REGULATOR. |
| |
| 2. FBC FG TABLE 402.4(21) IS NOT THE CORRECT TABLE FOR |
| THE SIZING OF THE 2PSI POLYETHYLENE PIPING FROM METER |
| TO BUILDING. PER WPB FBC 107.2.1, PROVIDE CORRECT TABLE |
| (SEE TABLE 402.4(22). |
| |
| 3.A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF THE MP REGULATOR AT THE ENTRY POINT TO THE |
| BUILDING PER FBC FG 409.4. |
| |
| 4.THE DEVICE AT THE LOCATION OF THE EMERGENCY SHUTOFF |
| VALVE IS LABELED PRV. AN EMERGENCY SHUT OFF VALVE IS |
| NOT INDICATED. PER WPB FBC 107.2.1, CLARIFY AND |
| IDENTIFY THE EMERGENCY SHUTOFF VALVE. |
| |
| 5. IT IS NOTED THAT THE DEVELOPED LENGTH OF THE PIPING |
| IS 91 FEET. THE PIPING APPEARS TO BE SIZED BASED ON |
| EACH SYSTEM BEING A MAXIMUM OF 100 FEET WHEN APPLYING |
| THE CORRECT TABLES. PER WPB FBC 107.2.1, CONFIRM THAT |
| EACH SYSTEM, 2LB. AND LESS THAN 2LB. DOES NOT EXCEED |
| 100? TOTAL LENGTH OR PROVIDE THE ACTUAL MAXIMUM LENGTH |
| FOR EACH SYSTEM. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 21080885 7310 GEORGIA AVE # 1 |
| MASTER PERMIT 19120571 |