Plan Review Notes For Permit 21080880 |
Permit Number |
21080880 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-08-31 08:02:46 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | APPROVAL (TPO 18-0523.05) REQUIRES ADDITIONAL SIGNED | | AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT OR | | ENGINEER FOR ROOF WIND ZONES 3 WHICH REQUIRE A HIGHER | | PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL | | (-60) - SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT | | APPROVAL. DRAWING S101 FROM PERMIT NUMBER 20120907 | | SHOWS ZONE 3 WIND PRESSURE OF (-72) | | 2) PLEASE PROVIDE THE FRONT PAGES OF THE PRODUCT | | APPROVAL FOR THE (TPO 18-0523.05). | | 3) PLEASE PROVIDE THE FRONT PAGES FOR THE PRODUCT | | APPROVAL FOR THE SHINGLES (FL10124) |
|