Plan Review Notes
Plan Review Notes For Permit 21080880
Permit Number 21080880
Review Stop B
Sequence Number 2
Notes
Date Text
2021-08-27 13:13:37ROOFING SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080880
  
 1- COMMENTS DONE BY JONATHAN BROOKS JR. ON THE FIRST
 REVIEW WERE NOT ADDRESSED.
 SEE COPY OF COMMENTS BELOW AND PROPERLY ADDRESS THEM
 AND RESUBMIT.
  
 2- PROVIDE SPECIFICATIONS CLEARLY SHOWING HOW COMPLYING
 WITH THE NEW 2020 CODE REQUIREMENT FOR SHINGLES ROOFING
 UNDERLAYMENT SEC. 1507.1.1.1 FBC-BUILDING.
 NOTE: PROVIDE PRODUCT APPROVAL FOR ROOF SHINGLES
 UNDERLAYMENT TO BE USED. FAC 61G20-3.001.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 ORIGINAL COMMENTS:
  
 JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.3.4.1. SUBMITTED MIAMI-DADE COUNTY NOA
 NO.: 18-0523.05 & PRODUCT APPROVAL FL10124-R30 SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2. SUBMITTED PRODUCT APPROVAL FL10124-R28 HAS BEEN
 REVISED TO FL10124-R30. PLEASE PROVIDE A COMPLETE SET.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3.
 3. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 18-0523.05 IS INCOMPLETE. PLEASE PROVIDE THE FOLLOWING:
 PAGES #1-11 & LIMITATIONS PAGE #89. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS.
 4. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND
 SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER MIAMI-DADE NOA. NO.
 18-0523.05 LIMITATIONS #7.
 5. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH
 TESTING APPLICATION STANDARD TAS 105 AND RAS 117 AND/OR
 RAS 137 AS REQUIRED BY STEEL DECK SYSTEM LIMITATIONS #1
 OF MIAMI-DADE NOA NO. 18-0523.05 SIGNED AND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT.
 6. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA
 NO.: 19-0917.02 COVERS MULTIPLE PRODUCTS & SYSTEMS E(1)
 ? E(4). ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved