Date |
Text |
2021-08-19 12:46:34 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC B 107.3.4.1. SUBMITTED MIAMI-DADE COUNTY NOA |
| NO.: 18-0523.05 & PRODUCT APPROVAL FL10124-R30 SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| 2. SUBMITTED PRODUCT APPROVAL FL10124-R28 HAS BEEN |
| REVISED TO FL10124-R30. PLEASE PROVIDE A COMPLETE SET. |
| ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER |
| RULE 61G20-3. |
| 3. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA |
| 18-0523.05 IS INCOMPLETE. PLEASE PROVIDE THE FOLLOWING: |
| PAGES #1-11 & LIMITATIONS PAGE #89. ALL APPLICABLE |
| DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| THE PRODUCT APPROVAL DRAWINGS. |
| 4. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND |
| SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR |
| PERIMETERS AND CORNERS AS PER MIAMI-DADE NOA. NO. |
| 18-0523.05 LIMITATIONS #7. |
| 5. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH |
| TESTING APPLICATION STANDARD TAS 105 AND RAS 117 AND/OR |
| RAS 137 AS REQUIRED BY STEEL DECK SYSTEM LIMITATIONS #1 |
| OF MIAMI-DADE NOA NO. 18-0523.05 SIGNED AND SEALED BY A |
| FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF CONSULTANT. |
| 6. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA |
| NO.: 19-0917.02 COVERS MULTIPLE PRODUCTS & SYSTEMS E(1) |
| ? E(4). ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| |