 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.3.4.1. SUBMITTED MIAMI-DADE COUNTY NOA
 NO.: 18-0523.05 & PRODUCT APPROVAL FL10124-R30 SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2. SUBMITTED PRODUCT APPROVAL FL10124-R28 HAS BEEN
 REVISED TO FL10124-R30. PLEASE PROVIDE A COMPLETE SET.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3.
 3. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 18-0523.05 IS INCOMPLETE. PLEASE PROVIDE THE FOLLOWING:
 PAGES #1-11 & LIMITATIONS PAGE #89. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS.
 4. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND
 SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER MIAMI-DADE NOA. NO.
 18-0523.05 LIMITATIONS #7.
 5. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH
 TESTING APPLICATION STANDARD TAS 105 AND RAS 117 AND/OR
 RAS 137 AS REQUIRED BY STEEL DECK SYSTEM LIMITATIONS #1
 OF MIAMI-DADE NOA NO. 18-0523.05 SIGNED AND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT.
 6. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA
 NO.: 19-0917.02 COVERS MULTIPLE PRODUCTS & SYSTEMS E(1)
 ? E(4). ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  