Plan Review Notes
Plan Review Notes For Permit 21080731
Permit Number 21080731
Review Stop NFIP
Sequence Number 3
Notes
Date Text
2022-06-27 16:05:06NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC)
 COMMENTS PER FB107.
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 1. SECTION AA) GARAGE SQUARE FOOTAGE STATES 575SF. PLAN
 PAGE A100. STATES GARAGE IS 667SF.
 (PLAN REVIEW COMMENTS BY CARLOS CORDEO-LUZA STATES THE
 GARAGE IS 647. ENTER CORRECT DATA ON LINE A9A) OF EC)
  
 2. SECTION A9B) NUMBER OF FLOOD OPENINGS STATES N/A.
 PLAN PAGE AOOO SHOWS 2 FLOOD OPENINGS. (NOT CORRECTED)
  
 3. A9C) TOTAL NET AREA STATES N/A. THIS DATA WILL BE
 FROM THE TYPE OF FLOOD VENTS INSTALLED. ENGINEERED OR
 NON-ENGINEERED. (NOT CORRECTED)
  
 4. SECTION A9D) ENGINEERED FLOOD OPENINGS STATES NO. IF
 NON-ENGINEERED FLOOD OPENINGS ARE INSTALLED, PROVIDE A
 DETAIL BY A QUALIFIED DESIGN PROFESSIONAL, SIGNED AND
 SEALED. (INCORRECT DATA STILL ENETERD)
  
 5. SECTION C2D) TOP OF GARAGE FLOOR STATES 7.7FT. PLAN
 PAGE A100 STATES 6.6FT. (INCORRECT DATA STILL ENETERD)
  
 6. C2E) LOWEST ELEVATION OF MACHINERY STATES N/A.
 MACHINERY SERVICING THE BUILDING SHALL BE AT OR ABOVE
 THE DFE OF 8.0FT NAVD. (ENTER CORRECT DATA)
  
 7. C2F) LOWEST ADJACENT GRADE. REQUIRED. (DATA ENTERED
 APPEARS TO BE INCORRECT. PLEASE REFERENCE SITE DRAINAGE
 PLAN PAGE C-1 FOR DATA)
  
 8. C2G) HIGHEST ADJACENT GRADE. REQUIRED. (DATA ENTERED
 APPEARS TO BE INCORRECT. PLEASE REFERENCE SITE DRAINAGE
 PLAN PAGE C-1 FOR DATA)
  
 9. SECTION D COMMENTS: TYPE OF EQUIPMENT AND LOCATION
 REQUIRED. (SEE DIRECTIONS IN COMMENTS NARRATIVE BLOCK)
 (NOT ADDRESSED)
  
 10.
  
 PROVISO: PLAN PAGE S1 - UNDER CONSTRUCTION EC REQUIRED
 AT PLACEMENT OF 1ST FLOOR.
  
 C/O HOLD: FINISHED CONSTRUCTION EC REQUIRED PRIOR TO
 C/O.
  
 NEW COMMENT:
  
 11. C2B) DATA MISSING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  