2022-04-06 13:56:09NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC)
 COMMENTS PER FB107.
  
 1. SECTION AA) GARAGE SQUARE FOOTAGE STATES 575SF. PLAN
 PAGE A100. STATES GARAGE IS 667SF.
 2. SECTION A9B) NUMBER OF FLOOD OPENINGS STATES N/A.
 PLAN PAGE AOOO SHOWS 2 FLOOD OPENINGS.
 3. A9C) TOTAL NET AREA STATES N/A. THIS DATA WILL BE
 FROM THE TYPE OF FLOOD VENTS INSTALLED. ENGINEERED OR
 NON-ENGINEERED.
 4. SECTION A9D) ENGINEERED FLOOD OPENINGS STATES NO. IF
 NON-ENGINEERED FLOOD OPENINGS ARE INSTALLED, PROVIDE A
 DETAIL BY A QUALIFIED DESIGN PROFESSIONAL, SIGNED AND
 SEALED.
 5. SECTION C2D) TOP OF GARAGE FLOOR STATES 7.7FT. PLAN
 PAGE A100 STATES 6.6FT.
 6. C2E) LOWEST ELEVATION OF MACHINERY STATES N/A.
 MACHINERY SERVICING THE BUILDING SHALL BE AT OR ABOVE
 THE DFE OF 8.0FT NAVD.
 7. C2F) LOWEST ADJACENT GRADE. REQUIRED DATA NOT
 AVAILABLE. SITE DRAINAGE PLAN HAS NOT BEEN SUBMITTED
 FOR REVIEW.
 8. C2G) HIGHEST ADJACENT GRADE. REQUIRED DATA NOT
 AVAILABLE. SITE DRAINAGE PLAN HAS NOT BEEN SUBMITTED
 FOR REVIEW.
 9. SECTION D COMMENTS: TYPE OF EQUIPMENT AND LOCATION
 REQUIRED. (SEE DIRECTIONS IN COMMENTS NARRATIVE BLOCK)
 10. ELEVATION CERTIFICATE IS MISSING PAGES 5 AND 6.
 (PHOTOS). FEMA REQUIRES A COMPLETE EC. NOTE: NO PHOTOS
 ARE REQUIRED FOR THE CONSTRUCTION DRAWING EC.
  
 PROVISO: PLAN PAGE S1 - UNDER CONSTRUCTION EC REQUIRED
 AT PLACEMENT OF 1ST FLOOR.
  
 C/O HOLD: FINISHED CONSTRUCTION EC REQUIRED PRIOR TO
 C/O.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  