2021-12-29 14:13:09 | PLAN REVIEW PLUMBING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: A PLUMBING SUB-PERMIT IS REQUIRED. |
| |
| 1. CORRECT BUILDING CODE REFERENCE ON PLAN PAGE P102 |
| FROM FBC 2017 TO FBC 2020. |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 2. PROVIDE SHOWER PAN DETAIL. |
| P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1 |
| P2709.3 SHOWER PAN LINING INSTALLATION. |
| |
| 3. MASTER BATH GROUP IS ON A CLOSED VENT SYSTEM. |
| P3101.2.1VENTING REQUIRED. |
| EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN |
| ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN |
| THIS CHAPTER. |
| P3108.2.2VERTICAL WET VENT. |
| THE DRY-VENT CONNECTION FOR A VERTICAL WET-VENT SYSTEM |
| SHALL BE AN INDIVIDUAL VENT OR COMMON VENT FOR THE MOST |
| UPSTREAM FIXTURE DRAIN. |
| P3102.2INSTALLATION. |
| THE REQUIRED VENT SHALL BE A DRY VENT THAT CONNECTS TO |
| THE BUILDING DRAIN OR AN EXTENSION OF A DRAIN THAT |
| CONNECTS TO THE BUILDING DRAIN. SUCH VENT SHALL NOT BE |
| AN ISLAND FIXTURE VENT AS PERMITTED BY SECTION P3112. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |