2021-11-01 13:21:121) SHEET M1.1: THE OUTDOOR AIR CALCULATIONS FOR THE
 MEETING/CONFERENCE ROOM IS LOW. PLEASE PROVIDE OUTDOOR
 AIR CALCULATIONS FOR THIS USE OF SPACE ACCORDING TO FBC
 M 403.3.1.1 AND TABLE 403.3.1.1. THE CORRECT OUTDOOR
 AIR FOR THIS SPACE IS 601 CFM.
  