2021-09-09 08:20:391ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21080643
 9/9/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P0.1 & P1.1. PROVIDE A PLUMBING FIXTURE
 SCHEDULE THAT INCLUDES THE MOP SINK, BREAKROOM SINK,
 FAUCETS, WASHING MACHINE- SECTIONS 406, 418, & 424 FBC
 P.
  
 2) P0.1 & P1.1: SHOW THE LOCATIONS OF REQUIRED WATER
 HAMMER ARRESTORS AND BACKFLOW PREVENTERS ON SUPPLY
 LINES TO THE REFRIGERATOR ICE MAKERS IN THE BREAKROOM,
 AND THE ICE MACHINE IN THE EXISTING WAREHOUSE- SECTIONS
 604.9 & 608.3 FBC P. CLARIFY IF WALL BOXES WILL BE
 INSTALLED AT THE REFRIGERATOR LOCATIONS- SECTION
 107.2.1 WPB.
  
 3) ) P0.1 & P1.1: SHOW THE LOCATIONS OF REQUIRED WATER
 HAMMER ARRESTORS AND BACKFLOW PREVENTERS ON SUPPLY
 LINES TO THE WASHING MACHINE IN THE EXISTING WAREHOUSE-
 SECTIONS 604.9 FBC P. CLARIFY IF A WALL BOXES WILL BE
 INSTALLED AT THE MACHINE LOCATION- SECTION 107.2.1 WPB.
  
 4) P0.1 & P1.1: PROVIDE AN INTERCEPTOR FOR THE WASHING
 MACHINE DISCHARGE- SECTION 1003.6 FBC P. PLEASE NOTE AN
 INTERCEPTOR IS NOT AN INTEGRAL FILTER.
  
 5) P0.1 & P1.1: PLEASE REVIEW AND SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS FOR THE ICE MACHINE TO
 VERIFY A FLOOR DRAIN IS NOT REQUIRED TO CONVEY ICE
 DRAINAGE OR CONDENSATION FROM THE MACHINE- SECTION
 314.2.1 FBC P.
  
 6) P1.1: SHOW A 2-INCH STANDPIPE CONNECTIONG TO A
 3-INCH STACK AT THE WASHING MACHINE- SECTION 406.1 FBC
 P.
  
 7) A3.0: PAINTED GWB IS NOT APPROVED FOR INSTALLATION
 ON THE WALLS SURROUNDING THE MOP SINK. A SMOOTH, HARD,
 NONABSORBENT SURFACE MATERIAL IS REQUIRED TO BE
 INSTALLED TO A HEIGHT OF NOT LESS THAN 4 FT. ABOVE THE
 FLOOR- SECTION 1210.2.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  