2021-09-09 08:20:39 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21080643 |
| 9/9/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P0.1 & P1.1. PROVIDE A PLUMBING FIXTURE |
| SCHEDULE THAT INCLUDES THE MOP SINK, BREAKROOM SINK, |
| FAUCETS, WASHING MACHINE- SECTIONS 406, 418, & 424 FBC |
| P. |
| |
| 2) P0.1 & P1.1: SHOW THE LOCATIONS OF REQUIRED WATER |
| HAMMER ARRESTORS AND BACKFLOW PREVENTERS ON SUPPLY |
| LINES TO THE REFRIGERATOR ICE MAKERS IN THE BREAKROOM, |
| AND THE ICE MACHINE IN THE EXISTING WAREHOUSE- SECTIONS |
| 604.9 & 608.3 FBC P. CLARIFY IF WALL BOXES WILL BE |
| INSTALLED AT THE REFRIGERATOR LOCATIONS- SECTION |
| 107.2.1 WPB. |
| |
| 3) ) P0.1 & P1.1: SHOW THE LOCATIONS OF REQUIRED WATER |
| HAMMER ARRESTORS AND BACKFLOW PREVENTERS ON SUPPLY |
| LINES TO THE WASHING MACHINE IN THE EXISTING WAREHOUSE- |
| SECTIONS 604.9 FBC P. CLARIFY IF A WALL BOXES WILL BE |
| INSTALLED AT THE MACHINE LOCATION- SECTION 107.2.1 WPB. |
| |
| 4) P0.1 & P1.1: PROVIDE AN INTERCEPTOR FOR THE WASHING |
| MACHINE DISCHARGE- SECTION 1003.6 FBC P. PLEASE NOTE AN |
| INTERCEPTOR IS NOT AN INTEGRAL FILTER. |
| |
| 5) P0.1 & P1.1: PLEASE REVIEW AND SUBMIT THE |
| MANUFACTURER'S SPECIFICATIONS FOR THE ICE MACHINE TO |
| VERIFY A FLOOR DRAIN IS NOT REQUIRED TO CONVEY ICE |
| DRAINAGE OR CONDENSATION FROM THE MACHINE- SECTION |
| 314.2.1 FBC P. |
| |
| 6) P1.1: SHOW A 2-INCH STANDPIPE CONNECTIONG TO A |
| 3-INCH STACK AT THE WASHING MACHINE- SECTION 406.1 FBC |
| P. |
| |
| 7) A3.0: PAINTED GWB IS NOT APPROVED FOR INSTALLATION |
| ON THE WALLS SURROUNDING THE MOP SINK. A SMOOTH, HARD, |
| NONABSORBENT SURFACE MATERIAL IS REQUIRED TO BE |
| INSTALLED TO A HEIGHT OF NOT LESS THAN 4 FT. ABOVE THE |
| FLOOR- SECTION 1210.2.2 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |