Plan Review Notes For Permit 21080643 |
Permit Number |
21080643 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-08-30 11:04:30 | OFFICE BUILD OUT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | 1) DOORS NUMBER 1 AND 2 ARE PART OF A FIRE RATED WALL - | | ARE THE DOOR TO BE FIRE RATED? - IF SO, PLEASE SHOW THE | | HOURLY FIRE RATING AND SELF CLOSING ON THE DOOR | | SCHEDULE PER FBC 716 | | 2) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE OVERHEAD | | DOOR. ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND | | MARKED APPROVED BY THE DESIGNER OF RECORD FBC 107.3.4 |
|