2021-09-27 10:23:23 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| MAIN DWELLING UNIT |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. REF. PLAN PAGE A.0 FOR THE FOLLOWING COMMENTS: |
| 1A) CHANGE BUILDING CODE REFERENCE TO 7TH ED, 2020. |
| 1B) CHANGE NEC REFERENCE TO 2017 NEC. |
| |
| 2. PROVIDE BUILDING DATA: CONDITIONED SPACE, |
| UN-CONDITIONED SPACES. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 3. CANNOT VERIFY VALUE DUE TO LACK OF BUILDING DATA. |
| (SEE ABOVE) |
| CITY OF WPB CHPT109.3 BUILDING PERMIT VALUATIONS. |
| FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| BUILDING OFFICIAL |
| |
| 4. PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH |
| FBC R401.3 DRAINAGE. |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| |
| |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. |
| LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES WITHIN THE FIRST 10 FEET. |
| |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10 |
| FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE |
| DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING |
| FOUNDATION SHALL BE SLOPED A MINIMUM OF |
| 2 PERCENT AWAY FROM THE BUILDING. |
| |
| 5. PROVIDE AN ENERGY SUBMITTAL. |
| FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| STORIES. |
| FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE |
| ALTERNATIVE. |
| |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| 6. REF. PLAN PAGE A-3 FOR THE FOLLOWING COMMENT; |
| THE TEXT FOR THE INSTALLATION INSTRUCTIONS FOR THE |
| GABLE END SHEATHING AND WOOD BEAM HAS TEXT OVERRIDDEN. |
| CANNOT READ TEXT. PLEASE CORRECT. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 7. REF. PLAN PAGE S-4 FOR THE FOLLOWING COMMENT: |
| PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN |
| PRESSURES. |
| TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING |
| SCHEDULE FOR WOOD STRUCTURAL PANELS. |
| |
| 8. PROVIDE THE ICC-ES REPORT FOR THE SPRAY APPLIED |
| INSULATION. DESIGNER SHALL SELECT SYSTEM TO BE |
| INSTALLED. |
| FBC 107.3.4 FAC RULE 9N-3 REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD. |
| |
| 9. PROVIDE PRODUCT APPROVALS FOR OVERHEAD DOOR. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |