Plan Review Notes
Plan Review Notes For Permit 21080614
Permit Number 21080614
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-13 12:07:1008/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PLANS SUBMITTED DO NOT HAVE A CLEAR SCOPE OF
 WORK TO REFER TO ON EACH PAGE AND THE WORK LOCATION.
 WOULD YOU PLEASE PROVIDE A CLEAR AND DETAILED SCOPE OF
 THE NEW WORK TO BE DONE PER THE WPB AMENDMENTS TO THE
 FBC SEC.101.2 SCOPE?
  
 A. ON PAGE ONE, THE EXISTING KITCHEN IS NOT SHOWN,
 RANGE, AND THE HALF BATH FIXTURES. WOULD YOU PLEASE
 SHOW EXISTING AND NEW ON ALL PLANS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. ON PAGE TWO, IT SHOWS A LAUNDRY ROOM, THERE IS AN
 ELECTRICAL PERMIT ISSUED BUT LAUNDRY IS NOT SHOWN IN
 THOSE PLAN. A REVISION WILL BE REQUIRED FOR ELECTRICAL
 AND A MECHANICAL PERMIT AS WELL. PLEASE PROVIDE AN
 ISOMETRIC DIAGRAM FOR LAUNDRY FOR SANITARY AND WATER,
 AND SHOW THE SOURCE OF HOT WATER PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 C. ON PAGE THREE, THE BATHROOM NEXT TO THE CLOSET DOES
 NOT SAY IF IT IS EXISTING OR NEW. WOULD YOU PLEASE SHOW
 EXISTING AND NEW ON ALL PLANS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 D. ON PAGE FOUR, THE NEW LAYOUT SHOWS A BATHROOM; WE
 SUPPOSE IT'S NEW. WOULD YOU PLEASE PROVIDE DIMENSIONS
 FOR THE FIXTURES IN THE NEW BATHROOM AND LABEL THEM AS
 NEW PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. PLEASE PROVIDE
 AN ISOMETRIC DIAGRAM FOR THE NEW BATHROOM FOR SANITARY
 AND WATER, AND SHOW THE SOURCE OF HOT WATER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 PLUMBING.
  
 E. ON PAGES FIVE AND SIX, IF THERE ARE NO PLUMBING
 CHANGES, PLEASE NOTE THE SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. A BUILDING AND A MECHANICAL PERMIT MAY BE REQUIRED
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1. THAT WILL INCUR ANOTHER REVIEW STOP FROM
 OTHER TRADES AND MAY GENERATE COMMENTS FOR THE SCOPE OF
 WORK.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  