Plan Review Notes For Permit 21080607 |
Permit Number |
21080607 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-08-16 11:56:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED PROJECT INDICATES THE REMOVAL OF | | REQUIRED EXIT DOORS AND REPLACES THEM WITH ROLL UP | | DOORS THAT ARE NOT APPROVED EXIT DOORS. | | | | PLEASE REVIEW AND CORRECT THE NUMBER OF REQUIRED EXIT | | DOORS FOR THE EXISTING OCCUPANCY. | | | | | | 1A) PER # 1 ABOVE, PLEASE PROVIDE A LIFE SAFETY SHEET | | INDICATING THE ENTIRE FLOOR PLAN AND SHOWING THE | | OCCUPANCY LOAD CALCULATION, REQUIRED NUMBER OF EXITS, | | REQUIRED EXIT WIDTHS, TRAVEL PATHS, REQUIRED EXIT | | SEPARATION, EXIT SIGNS, EMERGENCY LIGHTING, ETC. | | | | PLEASE PROVIDE AS MUCH DETAIL AS POSSIBLE AS THE | | PROPOSED PLAN APPEARS TO INDICATED REQUIRED EXIT DOORS. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|