Plan Review Notes
Plan Review Notes For Permit 21080597
Permit Number 21080597
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2021-08-26 14:07:35PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE
 DEPARTMENT, WITH THE FOLLOWING COMMENTS:
  
 HYDROSTATIC TESTS. ALL PIPING AND ATTACHED
 APPURTENANCES SUBJECTED TO SYSTEM WORKING PRESSURE
 SHALL BE HYDROSTATICALLY TESTED AT 200 PSI (13.8 BAR)
 AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2
 HOURS.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved