2021-09-03 15:49:39 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21080552 |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS |
| BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE |
| WIND LOAD CALCULATIONS AS REQUIRED. |
| |
| 2- REVISE SHUTTERS INSTALLATION SCHEDULE: |
| A)REVISE TO REFLECT THE REVISED DESIGN PRESSURES. |
| REVISE DESIGN PRESSURES, ANCHOR SPACING AND EDGE |
| DISTANCE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B)MINIMUM EDGE DISTANCE SHOWN. CLEARLY SPECIFY IF THE |
| EDGE DISTANCE SHOWN INCLUDES THE STUCCO THICKNESS OR |
| NOT. THIS IS IMPORTANT BECAUSE IN THE FIELD THE ACTUAL |
| EDGE DISTANCE NEED TO BE LARGER THAN THE ONE SHOWN ON |
| THE SCHEDULE (TYPICALLY 1/2 MORE TO INCLUDE THE STUCCO |
| THICKNESS). |
| NOTE: BASED ON THE OPENING HEIGHT AND THE EDGE DISTANCE |
| SPECIFIED ON THE INSTALLATION SCHEDULE, IT LOOKS LIKE |
| THE SPECIFIED SHUTTER SPAN MAY BE TOO SHORT. THE EDGE |
| DISTANCE IS THE ONE THAT WILL BE VERIFIED IN THE FIELD. |
| IF TH EDGE DISTANCE IS LESS THAN THE SPECIFIED ONE, |
| THEN A REVISION WILL BE REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |