Plan Review Notes For Permit 21080536 |
Permit Number |
21080536 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-03-21 12:37:36 | REVISION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | 1) WALLS AROUND THE MOP SINK NEED TO COMPLY WITH FBC | | 1210.2.2 WALLS AND PARTITIONS. | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE | | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, | | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS | | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR | | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS | | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE) | | | | | | | | | | | | |
|