| 21080535 622 7TH ST |
| MASTER 19120504 LOT 7A REVISION |
| |
| 1ST REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| GENERAL COMMENT: DUE TO A CHANGE IN PROCESS, THE |
| BACKFLOW PERMIT AND GREASE INTERCEPTOR PERMITS ARE |
| REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| APPLICATION TO [email protected] . YOU WILL |
| RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| FOR NEW TOILET ROOM INDICATING THE FOLLOWING: |
| ***A) PROVIDE DIMENSIONS OF CLEARANCE AROUND A WATER |
| CLOSET; SHALL BE 60 INCHES MINIMUM MEASURED |
| PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES DEEP |
| MINIMUM FOR WALL HUNG WATER CLOSETS AND 59 INCHES DEEP |
| MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED |
| PERPENDICULAR TO THE REAR WALL PER FBC ACC 604.3.1 AND |
| 604.8.1.1. |
| ***B) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER |
| SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| CONTACT. |
| ***C) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| ?REFLECTING? SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND PER FBC ACC 603.3. |
| ***D) FLUSH CONTROLS SHALL BE HAND OPERATED OR |
| AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY |
| WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN |
| SIDE OF THE WATER CLOSET PER FBC ACC 604.6 |
| |
| 2.SHOW TOE AND KNEE CLEARANCE FOR THE LAVATORY AS |
| REQUIRED BY FBC ACC 306.2 AND 306.3 |
| |
| 3. A1.1A: PLUMBING FIXTURE SCHEDULE DOES NOT SHOW |
| DRINKING FOUNTAIN AS A REQUIRED FIXTURE. PER WPB FBC |
| 107.2.1 AND, PROVIDE A NOTE STATING "IN ACCORDANCE WITH |
| FBC PL 410.4, THIS RESTAURANT WILL PROVIDE DRINKING |
| WATER IN A FLAT BOTTOM CONTAINER FREE OF CHARGE." |
| |
| 4. P701/SANITARY RISER: PER FBC PL 1002.1, PROVIDE A |
| WATER SEAL TRAP FOR THE MOP SINK. |
| |
| 5. P801: REGARDING THE PLUMBING FIXTURE SCHEDULE |
| COMMENT REFERRING TO ARCHITECT, OWNERSHIP OR INTERIOR |
| DESIGN FOR SELECTION OF ALL FIXTURES AND ACCESSORIES, |
| PER WPB FBC 107.2.1, SUBMIT MANUFACTURER"S |
| SPECIFICATION/INSTALLATION MANUALS FOR ALL SCHEDULED |
| PLUMBING FIXTURES AND ACCESSORIES. |
| |
| 6. RE: P701/DETAIL 5; WATER HEATER DETAIL. DETAIL |
| INDICATES CONCRETE ANCHORS FOR WALL MOUNTED WATER |
| HEATER SUPPORT. A2.0B ENLARGED FLOOR PLANS INDICATE |
| METAL FRAMED PARTITIONS, NOT CONCRETE WALLS. PER WPB |
| FBC 107.2.1, CLARIFY AND CORRECT AS NECESSARY. |
| |
| 7.P701/DETAIL 5 NOTES PAN DRAIN TO THE MOP SINK; |
| P801/WATER HEATER SCHEDULE NOTE 3 CALLS FOR PAN DRAIN |
| TO NEAREST FLOOR DRAIN. PER WPB FBC 107.2.1, PLEASE |
| CLARIFY AND RECONCILE; IT IS NOTED THAT THERE IS NO |
| FLOOR DRAIN ON THE PLANS. |
| |
| 8.P701/DETAIL 5 SHOWS T&P RELIEF VALVE DISCHARGE |
| INDIRECTLY TO THE MOP SINK BUT SHOWS IT DISCHARGING TO |
| THE PAN DRAIN THROUGH AN AIR GAP. PER WPB FBC 107.2.1, |
| PLEASE CLARIFY AND RECONCILE; IT IS NOTED THAT THERE IS |
| NO FLOOR DRAIN ON THE PLANS. PLEASE NOTE THAT ANY |
| DISCHARGE TO A RECEPTACLE WILL REQUIRE AN AIR GAP PER |
| FBC PL 504.2. |
| |
| 9. N/A |
| |
| 10. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| STATING THE SAME. |
| |
| 11. GREASE INTERCEPTOR: PLEASE NOTE THAT PER FBC PL |
| 301.7 AND 303.2, THE INSTALLATION OF THE SCHIER GB-75 |
| GREASE INTERCEPTOR SHALL CONFORM TO A MINIMUM OF THE |
| MANUFACTURER'S RECOMMENDATIONS. IN ACCORDANCE WITH THE |
| GB-75 INSTALLATION GUIDE PAGE 8, 9 AND 10 OF 10, A |
| TWO-WAY CLEANOUT IS REQUIRED ON BOTH THE INLET AND |
| OUTLET SIDE OF THE GREASE INTERCEPTOR. |
| |
| 12. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TIEDOWN OF |
| GREASE INTERCEPTOR. PROVIDE DETAIL OF BURIED TANK. |
| PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF |
| EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE |
| FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. SEE THE |
| FOLLOWING: |
| ***A) PLEASE NOTE THAT PER FBC PL 301.7 AND 303.2, THE |
| INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR |
| SHALL CONFORM TO A MINIMUM OF THE MANUFACTURER'S |
| RECOMMENDATIONS. |
| ***B) TO BE CLEAR, PROVIDE A DETAIL FOR THE UNDERGROUND |
| INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR. |
| PLEASE REFER TO THE SCHIER GB-75 INSTALLATION GUIDE |
| PAGE 3, 8, 9 AND 10 OF 10 FOR DETAILS. PLEASE NOTE THE |
| REFERENCE TO TIE DOWNS AND MAKE A FINAL DETERMINATION |
| AS TO THE APPLICABILITY TO THIS PROJECT. |
| ***C) PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF |
| EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE |
| FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. |
| |
| 13. REGARDING THE SAMPLING POINT INSTALLED UPSTREAM OF |
| THE GB-75: |
| ***A) IN ACCORDANCE WITH THE SCHIER SV-10 INSTALLATION |
| GUIDE (SEE FBC PL 301.7 AND 303.2), THE SAMPLING POINT |
| SHALL BE DOWNSTREAM OF THE INTERCEPTOR. |
| ***B) PER WPB FBC 107.2.1, PLEASE SPECIFY THE SAMPLING |
| POINT DEVICE TO BE INSTALLED (SCHIER PRODUCT IS SV-10) |
| ***C) PLEASE NOTE THAT THE JURISDICTION ACCEPTS A |
| TWO-WAY CLEANOUT FOR USE AS A SAMPLING POINT |
| |
| 14. PER FBC PL 606.2(2), PROVIDE A SHUT-OFF VALVE ON |
| THE WATER SUPPLY PIPE TO EACH SILLCOCK/HOSE BIB. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |