2022-03-31 12:42:38 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 21080534 620 7TH ST |
| MASTER PERMIT 19120500 LOT 5B REVISION |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1. NEW COMMENT: DUE TO A CHANGE IN PROCESS, THE |
| BACKFLOW PERMIT AND GREASE INTERCEPTOR PERMITS ARE |
| REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| APPLICATION TO [email protected] . YOU WILL |
| RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| |
| 2.NEW COMMENT: GREASE INTERCEPTOR; PLEASE NOTE THAT PER |
| FBC PL 301.7 AND 303.2, THE INSTALLATION OF THE SCHIER |
| GB-75 GREASE INTERCEPTOR SHALL CONFORM TO A MINIMUM OF |
| THE MANUFACTURER'S RECOMMENDATIONS. IN ACCORDANCE WITH |
| THE GB-75 INSTALLATION GUIDE PAGE 8, 9 AND 10 OF 10, A |
| TWO-WAY CLEANOUT IS REQUIRED ON BOTH THE INLET AND |
| OUTLET SIDE OF THE GREASE INTERCEPTOR. |
| |
| 3.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE DETAIL |
| FOR TIEDOWN OF TANK. PROVIDE DETAIL OF BURIED TANK. |
| PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF |
| EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE |
| FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. SEE THE |
| FOLLOWING: |
| ***A) PLEASE NOTE THAT PER FBC PL 301.7 AND 303.2, THE |
| INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR |
| SHALL CONFORM TO A MINIMUM OF THE MANUFACTURER'S |
| RECOMMENDATIONS. |
| ***B) TO BE CLEAR, PROVIDE A DETAIL FOR THE UNDERGROUND |
| INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR. |
| PLEASE REFER TO THE SCHIER GB-75 INSTALLATION GUIDE |
| PAGE 3, 8, 9 AND 10 OF 10 FOR DETAILS. PLEASE NOTE THE |
| REFERENCE TO TIE DOWNS AND MAKE A FINAL DETERMINATION |
| AS TO THE APPLICABILITY TO THIS PROJECT. |
| ***C) PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF |
| EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE |
| FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. |
| |
| 4.NEW COMMENT: REGARDING THE SAMPLING POINT INSTALLED |
| UPSTREAM OF THE GB-75; |
| ***A) IN ACCORDANCE WITH THE SCHIER SV-10 INSTALLATION |
| GUIDE (SEE FBC PL 301.7 AND 303.2), THE SAMPLING POINT |
| SHALL BE DOWNSTREAM OF THE INTERCEPTOR. |
| ***B) PER WPB FBC 107.2.1, PLEASE SPECIFY THE SAMPLING |
| POINT DEVICE TO BE INSTALLED (SCHIER PRODUCT IS SV-10) |
| ***C) PLEASE NOTE THAT THE JURISDICTION ACCEPTS A |
| TWO-WAY CLEANOUT FOR USE AS A SAMPLING POINT |
| |
| |
| END OF COMMENTS. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 21080534 620 7TH ST |
| MASTER PERMIT 19120500 LOT 5B REVISION |
| |