Plan Review Notes For Permit 21080534 |
Permit Number |
21080534 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-09-20 10:34:03 | REVISION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | 1) DOOR OUT SWING SHOWN IN THE CORRIDOR BETWEEN THE | | BUILDINGS ON DRAWINGS A1.1, A1.0, A1.0A AND A2.0 | | APPEARS TO BLOCK EGRESS PER FBC 1005.7.1 DOORS. | | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED | | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY | | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE | | THAN ONE-HALF. | | | | 2) WALLS AROUND THE MOP SINK NEED TO COMPLY WITH FBC | | 1210.2.2 WALLS AND PARTITIONS. | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE | | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, | | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS | | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR | | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS | | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE) | | | | |
|