Plan Review Notes
Plan Review Notes For Permit 21080533
Permit Number 21080533
Review Stop P
Sequence Number 2
Notes
Date Text
2022-03-11 14:54:032ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21080533
 3/11/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P301 & P601: THE GREASE INTERCEPTOR SAMPLING
 PORT SHALL BE LOCATED ON THE OUTFLOW SIDE OF THE
 INTERCEPTOR ACCORDING TO THE MANUFACTURER?S
 SPECIFICATIONS- SEC. 1003.3.5 FBC P. A) AS PREVIOUSLY
 REQUESTED PLEASE PLACE A NOTE THAT THE GREASE
 INTERCEPTOR SHALL BE INSTALLED UNDER A SEPARATE PERMIT.
  
 2) A2.0A: A) LOCATIONS OF THE WATER CLOSET FLUSH
 CONTROLS ARE SHOWN ON THE WRONG SIDE- SEC. 604.6. B)
 KNEE AND TOE CLEARANCES FOR THE LAVATORIES NOT
 PROVIDED- SEC. 606.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  