Plan Review Notes For Permit 21080471 |
Permit Number |
21080471 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-09-02 16:32:09 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, THE OPENING SCHEDULE FASTENER SPACING IS | | DIFFERENT THAN WHAT IS INDICATED IN THE PRODUCT | | APPROVAL. FOR 12" ON CENTER SPACING THE PRODUCT | | APPROVAL INDICATES A WOOD SUBSTRATE. FOR A CONCRETE | | SUBSTRATE THE PRODUCT APPROVAL INDICATES A FASTENER | | SPACING OF 7.5" ON CENTER. PLEASE RE-EVALUATE AND | | RE-SUBMIT. |
|