2021-09-13 14:22:33 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTE: STATE EXPOSURE AND RISK CATEGORY OF STRUCTURE. |
| |
| 1. PROVIDE DESIGN WIND LOADS PER FBC RES CHAPT 3. |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). |
| |
| -OR- |
| |
| ASCE 7-16 (VULT 170MPH 3 SEC GUST / VASD 132MPH) |
| |
| 2. PROVIDE STRUCTURAL PLANS FOR THE PROPOSED ENCLOSURE. |
| |
| 2A) PROVIDE A FOUNDATION PLAN FOOTINGS/SLAB ON |
| GRADE/REINFORCING/TIE DOWNS |
| 2B) PROVIDE BUILDING PLANS WITH REQUIRED DIMENSIONS |
| 2C) PROVIDE A FLOOR PLAN WITH FLOOR TO FOUNDATION |
| CONNECTION DETAIL - OPTIONAL |
| 2D) PROVIDE A WALL PLAN WITH WALL TO FLOOR CONNECTION |
| DETAIL |
| 2E) PROVIDE A ROOF FRAMING PLAN WITH ROOF TO WALL |
| CONNECTION DETAIL - OPEN TRELLIS TYPE ROOF |
| |
| 3. PROVIDE A CONNECTOR SCHEDULE WITH REQUIRED FASTENERS |
| BASED ON DESIGN WIND LOADS. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |